The mass transfer rates as a function of the air-side heat transfer
coefficient (50–90 W/m2 C) are shown in Fig. 1 for refrigerant
temperatures of 8, 14, and 20 C, an air temperature of 7 C,
and a relative humidity of 60%. The mass transfer rate was measured
experimentally for air velocities of 1.5, 2.0, and 2.5 m/s.
The mass transfer rate of water vapor was also calculated from
the mathematical model of Ye et al. [28]. The experimentally measured
and calculated mass transfer rates were in good agreement
(with an error of less than 8%). However, as the refrigerant temperature
decreased, the agreement between the experimental and calculated
mass transfer rates worsened. The mathematical model of
Ye et al. [28] assumes that all properties within a control volume
are the average of the inlet and outlet conditions. As the temperature
difference between the air and the cold surface increases, so
does the variation in the temperature and humidity within the
control volume and the accuracy of the model prediction becomes
worse. According to the experimental results, when the refrigerant
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
ราคาโอนย้ายมวลเป็นฟังก์ชันของความร้อนของอากาศด้านถ่ายโอนสัมประสิทธิ์ (50 – 90 W/m2 C) มีแสดงใน Fig. 1 สำหรับออกแบบอุณหภูมิของ 8, 14 และ 20 C อุณหภูมิอากาศ 7 Cและความชื้นสัมพัทธ์ 60% มีวัดอัตราการถ่ายโอนมวลexperimentally สำหรับตะกอนอากาศ น่า 1.5, 2.0, 2.5 m/sนอกจากนี้ยังมีคำนวณอัตราการถ่ายโอนมวลของไอน้ำจากแบบจำลองแบบทางคณิตศาสตร์ของ Ye et al. [28] วัด experimentallyและอัตราการถ่ายโอนมวลที่คำนวณได้ในข้อตกลงที่ดี(มีข้อผิดพลาดน้อยกว่า 8%) อย่างไรก็ตาม เป็นอุณหภูมิน้ำยาครอบลดลง ข้อตกลงระหว่างการทดลอง และคำนวณโอนย้ายราคาที่ worsened โดยรวม แบบจำลองทางคณิตศาสตร์ของที่ทั้งหมดที่ ye et al. [28] ถือคุณสมบัติภายในปริมาตรควบคุมมีค่าเฉลี่ยของสภาพทางเข้าของและร้าน เป็นอุณหภูมิความแตกต่างระหว่างอากาศและเพิ่มพื้นผิวเย็น ดังนั้นไม่เปลี่ยนแปลงในอุณหภูมิและความชื้นภายในควบคุมปริมาณและความถูกต้องของการคาดการณ์ของแบบจำลองแย่ลง ตามผลการทดลอง เมื่อการออกแบบ
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 2:[สำเนา]
คัดลอก!
The mass transfer rates as a function of the air-side heat transfer
coefficient (50–90 W/m2 C) are shown in Fig. 1 for refrigerant
temperatures of 8, 14, and 20 C, an air temperature of 7 C,
and a relative humidity of 60%. The mass transfer rate was measured
experimentally for air velocities of 1.5, 2.0, and 2.5 m/s.
The mass transfer rate of water vapor was also calculated from
the mathematical model of Ye et al. [28]. The experimentally measured
and calculated mass transfer rates were in good agreement
(with an error of less than 8%). However, as the refrigerant temperature
decreased, the agreement between the experimental and calculated
mass transfer rates worsened. The mathematical model of
Ye et al. [28] assumes that all properties within a control volume
are the average of the inlet and outlet conditions. As the temperature
difference between the air and the cold surface increases, so
does the variation in the temperature and humidity within the
control volume and the accuracy of the model prediction becomes
worse. According to the experimental results, when the refrigerant
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 3:[สำเนา]
คัดลอก!
อัตราการถ่ายเทมวลที่เป็นฟังก์ชันของอากาศด้านการถ่ายเทความร้อน
สัมประสิทธิ์ ( 50 – 90 W / m2  C ) แสดงในรูปที่ 1 สำหรับอุณหภูมิของสารทำความเย็น
 8 ,  14 และ  20  C ที่อุณหภูมิ 7  C
และความชื้นสัมพัทธ์ 60 % การถ่ายเทมวลเท่ากันวัด
การทดลองสำหรับความเร็วลม 1.5 , 2.0 และ 2.5 m / s
อัตราการถ่ายเทมวลของไอน้ำก็คำนวณจาก
แบบจำลองทางคณิตศาสตร์ของเจ้า et al . [ 28 ] วัดและคำนวณอัตราการถ่ายเทมวลนี้

( อยู่ในข้อตกลงมีความคลาดเคลื่อนน้อยกว่า 8% ) แต่เป็นสารทำความเย็น
อุณหภูมิลดลง ข้อตกลงระหว่างทดลองและคำนวณอัตราการถ่ายโอนมวล
แย่ลง แบบจำลองทางคณิตศาสตร์ของ
ท่าน et al . [ 28 ] สันนิษฐานว่าคุณสมบัติในการควบคุมปริมาณ
เป็นค่าเฉลี่ยของการและเงื่อนไขที่เต้าเสียบ ขณะที่อุณหภูมิ
ความแตกต่างระหว่างอากาศและพื้นผิวเย็นเพิ่มขึ้นดังนั้น
ไม่การเปลี่ยนแปลงในอุณหภูมิและความชื้นภายในเล่ม
ควบคุมและความแม่นยำของแบบจำลองการทำนายกลายเป็น
แย่ จากผลการทดลอง เมื่อสารทำความเย็น
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.