The pump control system consists of independent subsystems, which are configured, in the SGS pump control algorithm.
The following subsystems will be configured:
- G Base91 pumps (P-2717 / P-2701 / P-2702)
- ULG 91 pumps (P-2703 / P-2704)
- LAWS pump (P-2705)
- SAP 9423 (additive) pumps (P-2706 / P-2707)
- SAP 7001 (additive) pumps (P-2708 / P-2709)
- ULG Additive pumps (P-2710 / P-2711)
- ADO Additive pumps (P-2712 / P-2713)
The pump control systems will perform sequential start/stop of pumps pending on product or additive demand and the calculated elapsed run time (to establish equal pump wear).
The PCS will have facilities for:
- Standard status display's
- Automatic/manual selection of pumps
- An adjustable pump running period (in which the pump keeps running) after the pump demand has disappeared
via the SGS operating station in the Despatch Office.