When a typical lead-acid cell is charged, lead sulfate
is converted to lead on the battery’s negative plate
and lead dioxide on the positive plate. Over-charge
reactions begin when the majority of lead sulfate has
been converted, typically resulting in the generation
of hydrogen and oxygen gas. At moderate charge
rates most of the hydrogen and oxygen will
recombine in sealed batteries. In unsealed batteries
however, dehydration will occur.