Table 5-1 Fault Codes
Error
Code Fault Source(s)
Fault Type
H=Hardware
S=Software Fault Description Possible Causes
0000 No Faults N/A N/A N/A
0010 AC Frequency Low S This fault indicates that the Utility
grid frequency is below or fell below
the setting of Min AC Freq: for
greater than 6 cycles. This fault is
auto-clearing. Once the Utility grid
frequency has recovered within the
acceptable operating range, the
Xantrex inverter qualifies the value
and automatically clears this fault
and resumes normal operation after
5-minute delay period.
• Utility grid frequency
fell below the
allowable limit