Prior to the removal of the original winding each of the
six split phases received a 60 Hz hipot test. Five passed the
(2E+1) kV level at 28.6 kV for 1 minute. One failed at 27
kV at a location just outside the slot which may have
resulted from tape separation as the coil was in a circuit
with high circulating current.