It's not easy to confirm the problem, we have some solution suggestion for your try.
1.Firstly, let's figure out whether your testing equipment has problem, pls take a photo of the testing equipment,
make sure the testing equipment is for 1-phase, power factor 1.0 not 0.8, some equipment is 1-phase but power factor is 0.8, so the genset output cannot be 100%.
2.If the testing equipment is no problem, we should adjust the engine, make the frequency between 53~54Hz when 0% loading,
so the frequency will be around 50Hz when 100% loading(15kw), see attached photo. Take photo of the 3-meters after engine start but with 0% loading.
3.If the adjust doesn't work, the problem should be the engine, there're many possibilities, this genset was delivered to you about 2-years ago,
so there might be too many incrustation inside the cooling tube of engine, which affect the engine power.
It's not easy to confirm the problem, we have some solution suggestion for your try.1.Firstly, let's figure out whether your testing equipment has problem, pls take a photo of the testing equipment, make sure the testing equipment is for 1-phase, power factor 1.0 not 0.8, some equipment is 1-phase but power factor is 0.8, so the genset output cannot be 100%.2.If the testing equipment is no problem, we should adjust the engine, make the frequency between 53~54Hz when 0% loading, so the frequency will be around 50Hz when 100% loading(15kw), see attached photo. Take photo of the 3-meters after engine start but with 0% loading.3.If the adjust doesn't work, the problem should be the engine, there're many possibilities, this genset was delivered to you about 2-years ago, so there might be too many incrustation inside the cooling tube of engine, which affect the engine power.
การแปล กรุณารอสักครู่..