3.4 Electric field measurement
The electric field distribution was measured on the four
apparatus at 2500 and 5000 h of testing. In each
measurement period, the test was stopped and 24 h later,
when the samples were dry, the electric field was measured
at test voltage (66.4 kVphase-ground). Nearly 5000 h after
the ageing test was completed, another electric field
measurement was only made on sample 4 in order to
validate the obtained results. During this period, the sample
mainly rested in dry conditions without voltage. In this
case, before doing the measurement, sample 4 was cleaned
up in order to remove the carbonised residues from its
insulating surface, and the achieved results are referred to
10 000 h.
Fig. 6 shows the obtained results for the different test
periods and each curve represents a period. For the
measurements carried out during the 2500 and 5000 h
periods, the curve corresponding to the 5000 h period for
sample 4 (Fig. 6d) shows abrupt changes from one point
to another, closer to the high-voltage electrode. It is
considered that such change is because of the tracking
damage observed on the insulation after 2500 h of testing
(Fig. 4). Therefore the performance of this curve could
indicate that the tracking is a risky condition for a further
failure, and that the equipment should be either replaced or
monitored frequently. The other curves, including those for
samples 1–3, show a smooth change from one point to
another, which is the expected performance for insulations
in good operating condition. These curves indicate that, for
the period in which they were obtained, the level of ageing
produced in the apparatus by this testing process is not a
failure risk.
The easy detachment of the carbonised residues on the
surface of sample 4 showed that erosion was slight, having
a depth less than 1 mm. For this reason, it is supposed that
such erosion is not a failure risk for the integrity of the
insulation, as long as the tracking is removed. The above
was verified with the electric field measurement at 10 000 h
as shown in Fig. 6d. The curve for the 10 000 h period
shows a smooth change from one point to another.
Therefore it can be said that the deformation observed after
3.4 Electric field measurement
The electric field distribution was measured on the four
apparatus at 2500 and 5000 h of testing. In each
measurement period, the test was stopped and 24 h later,
when the samples were dry, the electric field was measured
at test voltage (66.4 kVphase-ground). Nearly 5000 h after
the ageing test was completed, another electric field
measurement was only made on sample 4 in order to
validate the obtained results. During this period, the sample
mainly rested in dry conditions without voltage. In this
case, before doing the measurement, sample 4 was cleaned
up in order to remove the carbonised residues from its
insulating surface, and the achieved results are referred to
10 000 h.
Fig. 6 shows the obtained results for the different test
periods and each curve represents a period. For the
measurements carried out during the 2500 and 5000 h
periods, the curve corresponding to the 5000 h period for
sample 4 (Fig. 6d) shows abrupt changes from one point
to another, closer to the high-voltage electrode. It is
considered that such change is because of the tracking
damage observed on the insulation after 2500 h of testing
(Fig. 4). Therefore the performance of this curve could
indicate that the tracking is a risky condition for a further
failure, and that the equipment should be either replaced or
monitored frequently. The other curves, including those for
samples 1–3, show a smooth change from one point to
another, which is the expected performance for insulations
in good operating condition. These curves indicate that, for
the period in which they were obtained, the level of ageing
produced in the apparatus by this testing process is not a
failure risk.
The easy detachment of the carbonised residues on the
surface of sample 4 showed that erosion was slight, having
a depth less than 1 mm. For this reason, it is supposed that
such erosion is not a failure risk for the integrity of the
insulation, as long as the tracking is removed. The above
was verified with the electric field measurement at 10 000 h
as shown in Fig. 6d. The curve for the 10 000 h period
shows a smooth change from one point to another.
Therefore it can be said that the deformation observed after
การแปล กรุณารอสักครู่..

3.4 การวัดการกระจายสนามไฟฟ้าสนามไฟฟ้า
4
เครื่องมือวัดใน 2500 และ 5000 ชั่วโมงของการทดสอบ ในการวัดแต่ละ
ระยะเวลาการทดสอบถูกหยุด และ 24 ชั่วโมงต่อมา
เมื่อตัวอย่างแห้ง สนามไฟฟ้า วัด
ที่แรงดันทดสอบ ( เป็น kvphase พื้นดิน ) เกือบ 5 , 000 ชั่วโมงหลังจากการบ่มทดสอบเสร็จสมบูรณ์
อีก สนามไฟฟ้าการวัดผล ทำแค่ในตัวอย่าง 4 เพื่อ
ตรวจสอบผลการทดลอง ในช่วงเวลานี้ , ตัวอย่าง
ส่วนใหญ่พักในสภาพแห้ง ปราศจากแรงดัน ในกรณีนี้
, ก่อนที่จะทำการวัดตัวอย่าง 4 สะอาด
ขึ้นเพื่อลบ carbonised ตกค้างจาก
ฉนวนพื้นผิวและบรรลุผลจะเรียกว่า
รูป 10 , 000 ชั่วโมง6 แสดงผลการทดลองเพื่อทดสอบความแตกต่างและแต่ละโค้งแทน
ช่วงระยะเวลา สำหรับ
วัดการดําเนินการในช่วง 2500 และ 5000 H
ช่วงโค้งที่สอดคล้องกับระยะเวลา 5 , 000 H
ตัวอย่าง 4 ( รูปที่ 6 ) แสดงให้เห็นการเปลี่ยนแปลงอย่างฉับพลันจาก
จุดหนึ่งไปยังอีก ใกล้ไฟฟ้าแรงสูง . มันคือ
ถือว่าเปลี่ยนแปลงดังกล่าวเป็นเพราะการติดตาม
ความเสียหายที่พบในฉนวนหลัง 2500 h การทดสอบ
( รูปที่ 4 ) ดังนั้นประสิทธิภาพของเส้นโค้งนี้สามารถ
แสดงว่าติดตามคือ สภาวะที่มีความเสี่ยงสำหรับความล้มเหลวต่อไป
, และอุปกรณ์ที่ควรมีให้เปลี่ยนหรือ
ติดตามบ่อย เส้นโค้งอื่น รวมทั้งสําหรับ
ตัวอย่าง 1 – 3 , แสดงการเปลี่ยนแปลงที่ราบรื่นจากจุดหนึ่งไปยัง
อื่นซึ่งเป็นที่คาดหวังสำหรับฉนวน
ในภาวะ . เส้นโค้งเหล่านี้บ่งชี้ว่า สําหรับ
ระยะเวลาที่พวกเขาได้รับ ระดับของริ้วรอย
ผลิตในเครื่อง โดยกระบวนการทดสอบนี้ไม่ได้
ความเสี่ยงความล้มเหลว ปลดง่ายของ carbonised ตกค้างบนพื้นผิวของตัวอย่างที่ 4 พบว่า
ถูกกัดกร่อนเล็กน้อย มีความลึกน้อยกว่า 1 มม. . ด้วยเหตุผลนี้มันควรจะเป็นที่
เช่นการกัดเซาะไม่ใช่ความล้มเหลวความเสี่ยงสำหรับความสมบูรณ์ของ
ฉนวนตราบใดที่การติดตามจะถูกเอาออก ข้างบน
ยืนยันกับสนามไฟฟ้า วัดที่ 10 000 H
ดังแสดงในรูปที่ 6 . โค้งสำหรับ 10 000 H
แสดงระยะเวลาการเปลี่ยนแปลงที่ราบรื่นจากจุดหนึ่งไปยังอีก .
ดังนั้นจึงอาจกล่าวได้ว่า หลังจากการตรวจสอบ