5. If a wye-wye transformer connection is used, the ground relays
at breaker A can respond to a ground fault at location F3 that
requires coordinating the ground protection at breaker A with
local ground protection at the DG. It is the general practice at
industrial and commercial medium-voltage facilities to ground
generator neutrals with a resistor to limit ground current to
between 200-400A