(1) Smoke protection calculations analysis to substantiate the use of smoke-protected assembly seating as follows:
(a) Performance-based design methods approved by the AHJ
(b) Smoke exhaust and fresh aircontrol requirements per NFPA 92, Standard for Smoke Control Systems
(c) Smoke control assumptions, such as fire scenario description, fire size quantification, and smoke
development/smoke movement analysis
(b) Smoke maintained at a level 6 ft above the floor of the means of egress
(cd) Proposed testing protocol for smoke control system and pass/fail criteria
(d) Calculations for performance-based design methods accepted by the AHJ
(e) Smoke and fire modeling
(fe) Timed egress analysis and assumed flow rates and travel speeds
(g) Assumed flow rates and travel speed
(2) Sprinkler protection calculations, including an