The A-sensor is used to manage the cabinets refrigeration system
and is fi xated in a given position in the cabinet, not in storage space.
The location of the A sensor must not be altered.
The E-sensor is placed in the cabinet storage space and can be
moved around in the cabinet to get the desired reference point
for temperature. The E-sensor is the default display sensor and
reference for the alarms. The E-sensor has no effect on control of
the refrigeration system.
The A-sensor is calibrated if the actual temperature in the cabinet
does not match the setpoint, despite taking the hysteresis into
consideration. Calibration of A sensor is named “cA”.
The E-sensor is calibrated if the actual temperature in the cabinets
display, provided that the display sensor for reference is the
E-sensor, does not match the independent temperature monitoring
used for control. Calibration of E-sensor is named “cE”