3 Execution
3.1 Installation
3.1.1 In general, the Power cables shall be run in condults, In cable tray and shall be run
concealed in celling, floor, and wall or as indicated on the Drawings.
3.1.2 No wire shall be pulled into the condult system util it is complete in all details.
3.1.3 Lubricant shall be used to facilitate wire pulling. Lubricants shall be approved
for using with the insulation specified.
3.1.4 Splicing of cable wires shall be allowed only in the luminaries, receptacles and
proper junction box with an approved method of insulation. No splice shall be
made in conductors for instrument circuits or control circuits.