I had informed Khun Kaew for daily check and record water pressure in pipe line at pressure gauge for check leaks and let me know.
And the job pending is replace the water pressure relief Valve size 1” for fire pump at pump room by ACS construction service Company and test performance report from the GMT Company.
I understand the sprinkler system is now fully functional!
The valves have all been replaced around the resort, the jockey pump is on automatic BUT they can’t locate any leaks.
Is that the same information you have received from the contractor?
Is there anything else still to do with this or pending?
Noted, the issue as you mentioned came from the leslie valve size 1” was out of order of Jockey fire pump and water strainer was dilapidated of suction line for fire pump
And flow meter of firewater pipe discharge line was out of order for fire pump at CKBR site A. Khun Kaew has tested water pressure of fire hose reel cabinet last week as find attached.
F Y I, the ACS. construction service Company will be in CKBR tomorrow for firewater pipe leaking repairing and replace firewater valve on September 24 – 30, 2015 as find attached