In order to check the proper operation of the filter, close the low pressure 1/4" valve to the pressure differential switch for a period of 5 seconds. This will initiate the self-cleaning cycle: Check that the exhaust valve opens, that the scanners move upwards, and when they reach the top limit switch - verify that the exhaust valve closes