The most frequent complaints were rain water entered house through win การแปล - The most frequent complaints were rain water entered house through win ไทย วิธีการพูด

The most frequent complaints were r

The most frequent complaints were rain water entered house through window. There are two main reasons to the problem. Firstly, the faulty detailing where a concrete copping is placed at the bottom of the window opening (see Figure 16). When rain water hits the concrete copping at the bottom of the window, rain water then bounces into the interior space of the unit through gaps between the glass panes. Secondly, the quality of workmanship where gaps between wall openings and window frames is not water tight, water seepage occurred at gaps between window and wall. Water proofing problem especially at toilet and bath is very crucial. Good site supervision and workmanship is critically important to resolve the problem. Otherwise, it is very costly and troublesome if to carry out any remedial work after completion.With the overall unit size of 650 square feet, in order to provide bigger kitchen, yard and bathroom, other rooms might need to be reduced in size. Table 8 shows the size comparison for room function between the By-law 42 & 43 of Uniform Building By-Law (UBBL), CIS 2 and existing design (PPR 2000). It is important to highlight that even the existing design (PPR 2000) is not meeting the minimum unit size stated in the CIS 2. Although Bedroom 3 received the lowest degree of satisfaction compared with bedroom 1 and bedroom 2 because of the existing odd corner, generally respondents are quite satisfied with the sizes of existing bedroom 1, bedroom 2 and bedroom 3. The size of existing kitchen is smaller than minimum as stated in CIS 2 but still complying with the minimum size as stated in UBBL. So, the question is should the revised design to comply with CIS 2 standard or is that any alternative size which is more appropriate.From the questionnaire survey, an alternative layout with kitchen size of 6.56 square meters (71 square feet) was proposed. The alternative kitchen size has received high degree of satisfaction compared with the existing kitchen size (see Figure 6). The space requirement for residential layout guideline, 1984 from Gravesham Borough Council, United Kingdom recommended that the minimum size for kitchen is 7.20 square meter or 77 square feet. Therefore, the minimum size for kitchen for the revised design should be aimed at 7.20 square meters (77 square feet). The space requirement for residential layout guideline, 1984 from Gravesham Borough Council, United Kingdom also recommended that if bathroom and water closet are to locate in the same room, the minimum size should be 3.50 square meters (38square feet). This size is much bigger than size as stated in CIS 2 as well as the existing bathroom size. As such, the minimum bathroom size for revised design if it is complete with water closet should be aimed at 3.50 square meters. Table 9 shows the selected rooms‟ function sizes of floor space requirements for residential layout guideline recommended by Gravesham Borough Council.
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
ร้องเรียนบ่อย ๆ บ้านป้อนน้ำฝนผ่านหน้าต่างได้ มีเหตุผลหลักสองประการปัญหา ประการแรก ผิดพลาดรายละเอียดที่คอนกรีต copping อยู่ที่ด้านล่างของการเปิดหน้าต่าง (ดูรูปที่ 16) เมื่อน้ำฝนฮิต copping คอนกรีตที่ด้านล่างของหน้าต่าง น้ำฝนแล้วเด้งเป็นพื้นที่ภายในของหน่วยโดยผ่านช่องว่างระหว่างบานหน้าต่างกระจก ประการที่สอง คุณภาพของผลงานที่ช่องว่างระหว่างช่องที่ผนังและกรอบหน้าต่างไม่แน่น น้ำ seepage น้ำเกิดขึ้นที่ช่องระหว่างหน้าต่างและผนัง ปัญหาพิสูจน์โดยเฉพาะอย่างยิ่งที่ห้องน้ำและอ่างอาบน้ำเป็นสิ่งสำคัญมาก เว็บไซต์ที่ดีดูแลและฝีมือเป็นสำคัญถึงการแก้ปัญหา ก็ลำบาก และค่าใช้จ่ายสูงมากถ้าการดำเนินงานใด ๆ ทำงานรวมหน่วยขนาด 650 ฟุต เพื่อให้ห้องครัวขนาดใหญ่ ลาน และห้อง น้ำ ห้องอื่น ๆ อาจจำเป็นต้องมีขนาดเล็กลง ตาราง 8 แสดงการเปรียบเทียบขนาดห้องฟังก์ชันระหว่าง By-กฎหมาย 42 และ 43 By กฎหมายอาคารชุดยูนิฟอร์ม (UBBL), CIS 2 และออกแบบที่มีอยู่ (กำลัง 2000) จึงต้องเน้นว่า แม้อยู่แบบ (PPR 2000) เป็นห้องประชุมขนาดหน่วยต่ำสุดที่ระบุใน CIS 2 3 ห้องนอนรับความพึงพอใจเมื่อเทียบกับห้องนอน 1 และห้องนอนเนื่องจากมุมไม่ปกติที่มีอยู่ในระดับต่ำ โดยทั่วไปผู้ตอบจะค่อนข้างพอใจกับขนาดของห้องนอน 1 ห้องนอน 2 และห้องนอน 3 อยู่ ขนาดของห้องครัวที่มีอยู่มีขนาดเล็กกว่าขั้นต่ำตามที่ระบุไว้ใน CIS 2 แต่ยังคง สอดคล้องกับค่าต่ำสุดตามที่ระบุไว้ใน UBBL ดังนั้น คำถามคือ ควรออกแบบปรับปรุงให้สอดคล้องกับมาตรฐาน CIS 2 หรือไม่ว่า ใด ๆ ทางเลือกขนาดที่เหมาะสมมากขึ้นจากการสำรวจแบบสอบถาม มีเสนอโครงการอื่น มีครัวขนาด 6.56 ตารางเมตร (71 ตารางฟุต) ขนาดห้องครัวอื่นได้รับความพึงพอใจเมื่อเทียบกับขนาดห้องครัวอยู่ในระดับสูง (ดูรูปที่ 6) ความต้องการพื้นที่สำหรับอยู่อาศัยเค้าโครงผลงาน 1984 จากสภา Borough Gravesham สหราชอาณาจักรแนะนำขนาดต่ำสุดของห้องครัวเป็น 7.20 เมตรหรือ 77 ตารางฟุต ดังนั้น ค่าต่ำสุดสำหรับห้องครัวออกแบบปรับปรุงควรมุ่งที่ 7.20 เมตร (77 ตารางฟุต) ความต้องการพื้นที่สำหรับอยู่อาศัยเค้าโครงผลงาน 1984 จากสภา Borough Gravesham สหราชอาณาจักรยังแนะนำว่า ถ้าห้องน้ำและส้วมจะค้นหาที่พัก ค่าต่ำสุดควร 3.50 เมตร (38square ฟุต) ขนาดนี้เป็นขนาดใหญ่กว่าขนาดตามที่ระบุไว้ใน CIS 2 ขนาดห้องน้ำที่มีอยู่ เช่น ขนาดห้องน้ำต่ำสุดสำหรับการออกแบบปรับปรุงถ้ามีส้วมควรมุ่งที่ 3.50 เมตร ตาราง 9 แสดงขนาดของฟังก์ชันของชั้นความต้องการพื้นที่สำหรับอยู่อาศัยเค้าโครงผลงานแนะนำสภา Borough Gravesham rooms‟ เลือก
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 2:[สำเนา]
คัดลอก!
The most frequent complaints were rain water entered house through window. There are two main reasons to the problem. Firstly, the faulty detailing where a concrete copping is placed at the bottom of the window opening (see Figure 16). When rain water hits the concrete copping at the bottom of the window, rain water then bounces into the interior space of the unit through gaps between the glass panes. Secondly, the quality of workmanship where gaps between wall openings and window frames is not water tight, water seepage occurred at gaps between window and wall. Water proofing problem especially at toilet and bath is very crucial. Good site supervision and workmanship is critically important to resolve the problem. Otherwise, it is very costly and troublesome if to carry out any remedial work after completion.With the overall unit size of 650 square feet, in order to provide bigger kitchen, yard and bathroom, other rooms might need to be reduced in size. Table 8 shows the size comparison for room function between the By-law 42 & 43 of Uniform Building By-Law (UBBL), CIS 2 and existing design (PPR 2000). It is important to highlight that even the existing design (PPR 2000) is not meeting the minimum unit size stated in the CIS 2. Although Bedroom 3 received the lowest degree of satisfaction compared with bedroom 1 and bedroom 2 because of the existing odd corner, generally respondents are quite satisfied with the sizes of existing bedroom 1, bedroom 2 and bedroom 3. The size of existing kitchen is smaller than minimum as stated in CIS 2 but still complying with the minimum size as stated in UBBL. So, the question is should the revised design to comply with CIS 2 standard or is that any alternative size which is more appropriate.From the questionnaire survey, an alternative layout with kitchen size of 6.56 square meters (71 square feet) was proposed. The alternative kitchen size has received high degree of satisfaction compared with the existing kitchen size (see Figure 6). The space requirement for residential layout guideline, 1984 from Gravesham Borough Council, United Kingdom recommended that the minimum size for kitchen is 7.20 square meter or 77 square feet. Therefore, the minimum size for kitchen for the revised design should be aimed at 7.20 square meters (77 square feet). The space requirement for residential layout guideline, 1984 from Gravesham Borough Council, United Kingdom also recommended that if bathroom and water closet are to locate in the same room, the minimum size should be 3.50 square meters (38square feet). This size is much bigger than size as stated in CIS 2 as well as the existing bathroom size. As such, the minimum bathroom size for revised design if it is complete with water closet should be aimed at 3.50 square meters. Table 9 shows the selected rooms‟ function sizes of floor space requirements for residential layout guideline recommended by Gravesham Borough Council.
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 3:[สำเนา]
คัดลอก!
ข้อร้องเรียนที่พบบ่อยที่สุดคือ ฝนตกน้ำเข้ามาในบ้านผ่านทางหน้าต่าง มีสองเหตุผลหลักสำหรับปัญหานี้ ประการแรก มีรายละเอียดที่เป็นคอนกรีตที่ไม่มีความรับผิดชอบจะอยู่ที่ด้านล่างของการเปิดหน้าต่าง ( รูปที่ 16 ) เมื่อฝนตกน้ำในคอนกรีต ไม่มีความรับผิดชอบ ที่ด้านล่างของหน้าต่างน้ำฝนแล้วเด้งเข้าไปในพื้นที่ของหน่วยผ่านช่องว่างระหว่างกระจกบาน . ประการที่สอง คุณภาพของผลงานที่ช่องว่างระหว่างผนังและหน้าต่างเป็นช่องน้ำไม่แน่น น้ำรั่วซึมที่เกิดขึ้นในช่องว่างระหว่างหน้าต่างและผนัง ปัญหาโดยเฉพาะอย่างยิ่งในน้ำห้องน้ำและอ่างอาบน้ำพิสูจน์อักษรมันสำคัญมากนะดูแลเว็บไซต์ที่ดีและผลงานที่เป็นวิกฤตที่สำคัญในการแก้ไขปัญหา อีกอย่าง มันเป็นบทเรียนราคาแพงมาก และยุ่งยากถ้าทำตามงานแก้ไขใด ๆหลังจากที่เสร็จสมบูรณ์ กับการรวมหน่วยขนาด 650 ฟุต เพื่อให้ครัวใหญ่ บ้านและห้องน้ำ ห้องอื่นๆ อาจต้องลดขนาดตารางที่ 8 แสดงเปรียบเทียบขนาดห้องฟังก์ชันระหว่างโดยกฎหมาย 42 & 43 อาคารชุดตามกฎหมาย ( ubbl ) , CIS และการออกแบบที่มีอยู่ ( PPR 2000 ) มันเป็นสิ่งสำคัญที่จะเน้นถึงการออกแบบที่มีอยู่ ( PPR 2000 ) คือประชุมหน่วยขนาดขั้นต่ำที่ระบุไว้ใน CIS 2แม้ว่าห้องนอน 3 ได้รับระดับต่ำสุดของความพึงพอใจเมื่อเทียบกับห้องนอน 1 และห้องนอน 2 เพราะมุมแปลกที่มีอยู่โดยทั่วไป ส่วนใหญ่จะค่อนข้างพอใจกับขนาด ของที่มีอยู่ ห้องนอน 1 ห้องนอน 2 และห้องนอน 3 ขนาดของห้องครัวที่มีอยู่มีขนาดเล็กกว่าขั้นต่ำตามที่ระบุใน CIS 2 แต่ยังคงมีขนาดขั้นต่ำตามที่ระบุใน ubbl . ดังนั้นคำถามคือ ควรปรับปรุง ออกแบบ เพื่อให้สอดคล้องกับมาตรฐาน CIS 2 หรือที่เลือกใด ๆขนาดที่จะเหมาะกว่า จากการสำรวจแบบสอบถาม รูปแบบทางเลือกกับขนาดห้องครัวของหนึ่งเมตร ( 15 ฟุต ) ถูกเสนอ ครัวทางเลือกขนาดได้รับระดับสูงของความพึงพอใจเมื่อเทียบกับที่มีอยู่ในครัว ขนาด ( ดูรูปที่ 6 )ความต้องการพื้นที่สำหรับแนวทางเค้าโครงที่อยู่อาศัย 1984 จากสภาเทศบาล gravesham สหราชอาณาจักรแนะนำว่าขนาดขั้นต่ำสำหรับห้องครัวคือ 7.20 เมตร หรือ 1 ฟุต ดังนั้นขนาดขั้นต่ำสำหรับห้องครัวเพื่อปรับปรุงการออกแบบควรจะมุ่งที่ 7.20 เมตร ( 77 ตารางเมตร ) ความต้องการพื้นที่สำหรับแนวทางการ ที่อยู่อาศัย1984 จากสภาเทศบาล gravesham , สหราชอาณาจักร ยังแนะนำว่า ถ้าห้องน้ำและส้วม เพื่อค้นหาในห้องเดียวกัน มีขนาดขั้นต่ำควรเป็น 3.50 เมตร ( เท้า 38square ) นี่ขนาดมันใหญ่กว่า ขนาดตามที่ระบุใน CIS 2 เช่นเดียวกับที่มีอยู่ห้องน้ำขนาด เช่นขั้นต่ำสำหรับการออกแบบห้องน้ำขนาดแก้ไขถ้ามันสมบูรณ์ด้วยตู้น้ำควรมุ่งที่ 3.50 เมตร ตารางที่ 9 แสดงห้องที่เลือก‟ฟังก์ชันขนาดของความต้องการพื้นที่สำหรับที่อยู่อาศัยรูปแบบแนวทางที่แนะนำโดยสภาเทศบาล gravesham .
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2026 I Love Translation. All reserved.

E-mail: