The equations presented above translate the expected behaviour of the control system: while TG < TREF, valve V1 remains
completely open while V2 is closed, thus directing the entire flow of exhaust gases, to the absorption cycle generator. If TG > TREF, V2 is gradually opened, partially directing the exhaust gases to the atmosphere. If the condition TG > TREF continues, V1 is then progressively closed.