interrupt fault current, in order to clear the fault in the transformer zone of protection the remote
line breakers must be tripped. As with the system shown in Figure 8.16, the relays at the remote
terminal must be set to ‘see’ into, but not beyond, the transformer. A common method of tripping
the remote terminals is to provide a single-phase ground switch at the transformer,