This short paper looks at the use of reverse osmosis (RO) in process water treatment applications and considers the process itself, the use of reverse osmosis membranes, and factors affecting water quality and plant performance.
Reverse osmosis is a process that industry uses to clean water, whether for industrial process applications or to convert brackish water, to clean up wastewater or to recover salts from industrial processes.
Reverse osmosis will not remove all contaminants from water as dissolved gases such as dissolved oxygen and carbon dioxide not being removed. But reverse osmosis can be very effective at removing other products such as trihalomethanes (THM's), some pesticides, solvents and other volatile organic compounds (VOC's).
The reverse osmosis process
In the reverse osmosis process cellophane-like membranes separate purified water from contaminated water. RO is when a pressure is applied to the concentrated side of the membrane forcing purified water into the dilute side, the rejected impurities from the concentrated side being washed away in the reject water.
RO can also act as an ultra-filter removing particles such as some micro-organisms that may be too large to pass through the pores of the membrane.
RO membranes
Common membrane materials include polyamide thin film composites (TFC), cellulose acetate (CA) and cellulose triacetate (CTA) with the membrane material being spiral wound around a tube, or hollow fibres bundled together.
Hollow fibre membranes have a greater surface area and hence capacity but are more easily blocked than spiral wound membranes.
RO membranes are rated for their ability to reject compounds from contaminated water. A rejection rate (% rejection) is calculated for each specific ion or contaminant as well as for reduction of total dissolved solids (TDS).
TFC membranes have superior strength and durability as well as higher rejection rates than CA/CTA membranes. They also are more resistant to microbial attack, high pH and high TDS. CA/CTA's have a better ability to tolerate chlorine.
Sulphonated polysulphone membranes (SPS) are chlorine tolerant and can withstand higher pH's and are best used where the feed water is soft and high pH or where high nitrates are of concern.