Inspect areas where chemicals are stored and handled to determine if emergency showers and eyewashes are provided. This emergency equipment must be accessible by a clear path of travel, clearly visible and within a reasonable travel distance. Travel distance to an eyewash station where corrosive materials are handled should not exceed 10 feet. Test a sample of these showers to determine if water flow is clean and of sufficient volume. Temperature controls are required in areas where the water is likely.