Using the BT200, set J11 back to 0.0, and then re-range the transmitter via a wet calibration method using the BT200 Brain Terminal (i.e. range change while applying actual inputs). The required level range is 0 to 80% (i.e. when the level in the vessel is 0% the tx transmitter output should be 4 mA, and when the level in the vessel is 80% the tx transmitter output should be 20 mA). The procedure for re-ranging using the BT200 and actual inputs is described on page 8-22. Note, parameters H10 and H11 are used to perform this wet calibration.