Dear N"Jib,
Please see below comment for your consideration & advise :-
Note : This comment is sent before you sent me the Wind force calculation.
++++
They submitted more information for the shopfront glass but this is just a kind of "trade practice of the glass thickness assuming 4 side fixing". For this we normally assume that the 4 sides is rigid. My challenge to this design is that the frame holding the glass is rather slim, ie 36 x 100 or 18 x 100 aluminium section ( They showed 2 but not sure what are they using. May be this could be a marginal case as not sure if Bangkok is subject to Typhoon. It can hardly considered as engineering calculation.
As for the facade, they are similar to before and keep saying the the truss is strong enough to take the vertical load and I believe they are. The missing information is how the vertical grille or the alucobond panel can transfer the wind load to this truss structure. May be this has yet to send to you.
From the drawing, I interpret the structure will be similar to the sketch but still missing some information as I marked red and green.