The limitation on deflection due to live load plus impact also can usually be waived
when considering the steel only for railway bridge design. The full composite section
should be designed as being sufficiently stiff to meet the deflection limitations.
Even if the steel section is adequate to carry the final design loading without
contribution from the concrete slab, composite action still must be investigated. The
neutral axis of the composite section will be higher on the cross-section than that for
the non-composite section. This will increase the stress range in the material below the
neutral axis, and fatigue details should be checked for this increased range.
While composite steel and concrete spans provide a stiff design with the benefits of a
ballasted-deck bridge, they are unlikely to be used to replace existing structures on
existing alignments. Compared to precast concrete deck panels, the additional time
required to form, place and cure the cast-in-place concrete deck of a composite span
requires off-line construction to minimize impact to rail operations. Parallel
construction of a composite span with a lateral roll-in during a train free window is one
way to work around this problem. Additionally, since the deck concrete is not under
compression from prestressing or post-tensioning, the use of a waterproofing system
to protect the deck may be warranted.
Where structure depth is limited by vertical clearances below the structure, a steel plate