Fig. 11.14 shows the swing curves without any control for a fault at
bus 34 cleared by tripping the line 34-35 at 0.267 s. The system is unstable;
generator 2 separates from the rest of the system. The lines 11-12 and 18-19
form the critical cutset. The same disturbance is simulated with a UPFC