400 Hz AC line drop compensation – adjustable from 0-5%. Units are factory set at
2% assuming a standard 30’ cable is used. If older or longer cables are used, increase
the setting to compensate for the increased resistance in the cable. The goal is to
maintain 115 VAC at the load bank with a 90 kVA load applied.
i. The steps to change the settings are the same as 3 above