Soft water : Water quality - moderate, pH lower than the standard
Vulcanized System : Water quality - moderate, ph lower than the standard, Total hardness is highly likely and Total Iron is trend higher.
Dying System : Water quality - moderate, pH lower than the standard
Boiler water : Water quality - remained relatively standard but found the The Total hardness is likely higher.
Recommend : - Water quality of Vulcanized System - Relatively low pH value, which causes rust in the system and low pH will cause pitting of pipes.
Should blow down sludge out of Boiler system
- Water of Dying System - Found a relatively low pH values, which are likely to cause corrosion in the future
- Boiler Water System - Found the parametor of water within the standard but found the Total Hardness is likely higher. This is the-
main reason for the formation of scale, which are used the scale inhibitor and dispersant chemical and corrosion inhibitor,
coupled with Blow Down will reduce the Total Hardness values.