Before to change in revised 1 the procedure I need some clarification about your remarks.
In point n.3 ferroresonance, for ANSI/NEMA this test is not routine but type test only, our proposal is performed the ferroresonance on one serial number as for ANSI type test and for the others serial numbers performed the test as for IEC, is feasible for you??
In point n.6 Transient response, this test is another type test, we need one week for verify if our laboratory have the technical resource for performed this test, in case affirmative the test will be introduced inside the procedure, in negative case the test should be repeat in an external laboratory.
For the others point, I have already modified the procedure as indicated.
I'm in waiting for your answer.