Important information for builders:
1. All the items marked with * should be provided by Builder
2.Concrete structural wall for brackets of guide rail landing doors and sill supports. Maximum reaction force of each bracket on wall is 3.7 KN. If not please contact KONE for confirmation.
3.Ventilation to ensure the temperature is within 5°C - 40°C humidity is 95% in well or machine room.
Reaction forces in pit shown on the drawing must be fulfilled. Pit is clean and dry.
4. Extra concrete plinth or cwt safety gear must be provided if there is any space that people can access under the pit.
5. Landing door cutout height should be accounted from the finished floor level. Floor sill is not allowed.
6. Nominal power main supply is TN-S type: l1+l2+l3+n+pe (TN-S)
7. A partition between the moving parts of different lifts if well contains several lifts. This partition shall extend at leastfrom the lowest point of travel of the car the counterweight or the balancing weight to a height of 2.5m above the
floor of the lowest landing. The width shall be as to prevent access from one pit to another
8. Elevator main switch and isolator can't have the function of earth leakage Protection.
9. The illumination intensity must at least be 50 LUX at 1m above the car roof pit floor. The machine room should beprovided with permanently installed electric lighting on the basis of at least 200 lux at floor level.