How is Surge Testing Performed?
The test can be performed on the motor winding without actually
connecting to the motor itself. The test equipment can be connected
to the load side of the motor starter. During the test a voltage
pulse is placed across two of the three windings while the third is
grounded. The magnitude of the pulse is approximately twice the
operating voltage plus 1000 volts. Therefore, low voltage starters
operating at 460 volts, are tested at approximately 2000 volts and
medium voltage starters, operating at 2400 volts, are tested at approximately
6000 volts. Pulses are produced at a frequency of 60
times per second and dissipate in approximately 100 microseconds.
The output, which is a dampened sign wave, is then monitored
on an oscilloscope. Since all three windings should have the same
surge patterns, the two patterns being monitored should appear as
a single overlapping wave. This procedure is repeated for all three
pairs of windings.
เป็นวิธีการดำเนินการทดสอบไฟกระชาก? การทดสอบสามารถดำเนินการในมอเตอร์หมุนไม่จริงการเชื่อมต่อกับมอเตอร์ตัวเอง อุปกรณ์ทดสอบสามารถเชื่อมต่อไปยังด้านโหลดเริ่มต้นของมอเตอร์ ในระหว่างการทดสอบแรงดันไฟฟ้าชีพจรจะถูกวางในสองในสามของขดลวดในขณะที่สามคือมีเหตุผล ขนาดของชีพจรจะอยู่ที่ประมาณสองเท่าของแรงดันไฟฟ้าปฏิบัติการบวก 1,000 โวลต์ ดังนั้นการเริ่มแรงดันต่ำการดำเนินงานที่ 460 โวลต์จะมีการทดสอบที่ประมาณ 2,000 โวลต์และเริ่มแรงดันไฟฟ้าขนาดกลาง, การดำเนินงานที่ 2,400 โวลต์จะมีการทดสอบที่ประมาณ6,000 โวลต์ พัลส์มีการผลิตที่ความถี่ 60 ครั้งต่อวินาทีและกระจายประมาณ 100 microseconds. การส่งออกซึ่งเป็นคลื่นสัญญาณชุบ, การตรวจสอบแล้วในสโคป เนื่องจากทั้งสามควรจะมีขดลวดเดียวกันรูปแบบคลื่นทั้งสองรูปแบบที่ถูกตรวจสอบควรจะปรากฏเป็นคลื่นเดียวที่ทับซ้อนกัน ขั้นตอนนี้ซ้ำสำหรับทั้งสามคู่ขดลวด