TCS Scaffolding shall be erected on

TCS Scaffolding shall be erected on a surface capable of supporting the intended loads or suspended from a structure that is capable of supporting the intended loads.

All vertical and horizontal scaffolding members must be erected and fixed to be plumb, level and squared with base plates placed to ensure adequate load bearing capacity. The scaffold must be set and maintained plumb to the full height of the scaffold.

Standards and ledgers shall be joined with joint pins or end to end sleeve couplers such that only one vertical joint is present in any one lift standard row and only one horizontal joint is present in a bay ledger line. End to end couplers (sleeve couplers) must be used when standards will be subject to upward loads or ledgers subject to tension (pull apart axial) loads.

Joints shall be located as close as possible to standards but not more than 300 mm (12") from the standard. If this is not possible, a 600 mm (24") parallel tube shall be coupled across the joint with at least two equally spaced right angle couplers on each side of the joint.

Ledgers and bay end transoms shall be placed on the inside of the vertical standards at the same elevation to ensure a level platform supported by intermediate transoms at the same elevation.

The scaffold shall have ledgers installed along the entire length of the inside and outside standards of the bay at each lift level. Ledgers shall be joined with joint pins or end to end sleeve couplers on straight runs to create continuous lengths and be connected to each standard.

Transoms shall be installed transversely between standards with couplers fastened to the standards immediately below the ledger. Boarding transoms shall be coupled above the ledgers and spaced as required for planking. Transoms must be 150 mm (6") to 300 mm (12") longer than the width. Transom extensions can be cantilevered to the maximum length required to support 2 planks. Planks on cantilevered transoms shall be secured and provide full contact with the transom to prevent movement or tilting.

A base (foot) ledger and transom shall be attached to the vertical standards no higher than 450 mm (18") from the bottom of the base plates along with a plan diagonal brace between the standards of the end bay to ensure the bay is rectangular and to provide bottom stability

Only right angle coupling shall be used for ledger to standard connections.

Couplings shall be installed to ensure the load forces are on the fixed side of the coupler never on the bolt side.

Check (safety) couplers shall be installed below or above load bearing couplers as necessary to prevent coupler slippage. This is especially important for underslung scaffolds and directly under trapeze tubes.

Scaffold couplers shall be tightened with scaffold wrenches only to the torque as indicated by the manufacturer. "Cheater bars" shall not be used.

All coupling connections of a scaffold lift shall be made secure and fully tightened before assembly of the next lift.
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
TCS Scaffolding shall be erected on a surface capable of supporting the intended loads or suspended from a structure that is capable of supporting the intended loads.All vertical and horizontal scaffolding members must be erected and fixed to be plumb, level and squared with base plates placed to ensure adequate load bearing capacity. The scaffold must be set and maintained plumb to the full height of the scaffold.Standards and ledgers shall be joined with joint pins or end to end sleeve couplers such that only one vertical joint is present in any one lift standard row and only one horizontal joint is present in a bay ledger line. End to end couplers (sleeve couplers) must be used when standards will be subject to upward loads or ledgers subject to tension (pull apart axial) loads.Joints shall be located as close as possible to standards but not more than 300 mm (12") from the standard. If this is not possible, a 600 mm (24") parallel tube shall be coupled across the joint with at least two equally spaced right angle couplers on each side of the joint.Ledgers and bay end transoms shall be placed on the inside of the vertical standards at the same elevation to ensure a level platform supported by intermediate transoms at the same elevation.The scaffold shall have ledgers installed along the entire length of the inside and outside standards of the bay at each lift level. Ledgers shall be joined with joint pins or end to end sleeve couplers on straight runs to create continuous lengths and be connected to each standard. Transoms shall be installed transversely between standards with couplers fastened to the standards immediately below the ledger. Boarding transoms shall be coupled above the ledgers and spaced as required for planking. Transoms must be 150 mm (6") to 300 mm (12") longer than the width. Transom extensions can be cantilevered to the maximum length required to support 2 planks. Planks on cantilevered transoms shall be secured and provide full contact with the transom to prevent movement or tilting.A base (foot) ledger and transom shall be attached to the vertical standards no higher than 450 mm (18") from the bottom of the base plates along with a plan diagonal brace between the standards of the end bay to ensure the bay is rectangular and to provide bottom stabilityOnly right angle coupling shall be used for ledger to standard connections.Couplings shall be installed to ensure the load forces are on the fixed side of the coupler never on the bolt side.Check (safety) couplers shall be installed below or above load bearing couplers as necessary to prevent coupler slippage. This is especially important for underslung scaffolds and directly under trapeze tubes.Scaffold couplers shall be tightened with scaffold wrenches only to the torque as indicated by the manufacturer. "Cheater bars" shall not be used.All coupling connections of a scaffold lift shall be made secure and fully tightened before assembly of the next lift.
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 2:[สำเนา]
คัดลอก!
TCS นั่งร้านจะถูกสร้างขึ้นบนพื้นผิวที่สามารถรองรับโหลดที่ตั้งใจไว้หรือห้อยลงมาจากโครงสร้างที่มีความสามารถในการรองรับการโหลดที่ตั้งใจไว้ก.

สมาชิกนั่งร้านแนวตั้งและแนวนอนทุกคนจะต้องสร้างและคงจะเป็นลูกดิ่งระดับและยืดด้วยแผ่นฐานวาง เพื่อให้แน่ใจว่ากำลังการผลิตไฟฟ้าแบริ่งเพียงพอ นั่งร้านจะต้องตั้งค่าและการบำรุงรักษาลูกดิ่งความสูงเต็มรูปแบบของนั่งร้าน.

มาตรฐานและบัญชีแยกประเภทจะสมทบกับหมุดร่วมกันหรือจบสิ้นเพลาแขนดังกล่าวว่ามีเพียงหนึ่งร่วมกันในแนวตั้งที่มีอยู่ในแถวมาตรฐานลิฟท์เพียงหนึ่งเดียวและร่วมกันในแนวนอน มีอยู่ในบรรทัดอ่าวบัญชีแยกประเภท สุดท้ายจบเพลา (เพลาแขน) จะต้องใช้เมื่อมาตรฐานจะต้องมีการโหลดขึ้นหรือบัญชีแยกประเภทขึ้นอยู่กับความตึงเครียด (ดึงแกนออกจากกัน) โหลด.

ข้อต่อจะต้องตั้งอยู่ใกล้ที่สุดเท่าที่เป็นไปได้มาตรฐาน แต่ไม่เกิน 300 มิลลิเมตร (12 " ) จากมาตรฐาน. ถ้านี้เป็นไปไม่ได้ 600 มิลลิเมตร (24 ") หลอดขนานจะต้องควบคู่ไปทั่วทั้งร่วมกันอย่างน้อยสองเท่ากันเว้นเพลามุมขวาในแต่ละด้านของการร่วมทุน.

บัญชีแยกประเภทและ transoms อ่าวท้ายจะถูกวางไว้ ด้านในของแนวตั้งมาตรฐานที่ระดับความสูงเดียวกันเพื่อให้แน่ใจว่าแพลตฟอร์มระดับการสนับสนุนจาก transoms กลางที่ระดับความสูงเดียวกัน.

นั่งร้านต้องมีบัญชีแยกประเภทการติดตั้งตามความยาวทั้งหมดของภายในและภายนอกมาตรฐานของอ่าวในแต่ละระดับยก บัญชีแยกประเภทจะสมทบกับหมุดร่วมกันหรือจบสิ้นเพลาแขนวิ่งตรงไปที่การสร้างความยาวอย่างต่อเนื่องและสามารถเชื่อมต่อกับแต่ละมาตรฐาน.

transoms จะได้รับการติดตั้งตามขวางระหว่างมาตรฐานกับเพลายึดมาตรฐานที่อยู่ต่ำกว่าบัญชีแยกประเภท transoms หอพักจะต้องควบคู่ไปข้างต้นบัญชีแยกประเภทและเว้นระยะเป็นสิ่งจำเป็นสำหรับการปูกระดาน transoms จะต้องเป็น 150 มิลลิเมตร (6 ") ถึง 300 มิลลิเมตร (12") นานกว่าความกว้าง ส่วนขยายกรอบวงกบสามารถแพร่งเพื่อความยาวสูงสุดที่จำเป็นในการสนับสนุน 2 แผ่น แผ่นบน transoms แพร่งจะต้องได้รับการรักษาความปลอดภัยและให้ติดต่อที่เต็มไปด้วยกรอบวงกบเพื่อป้องกันไม่ให้การเคลื่อนไหวหรือเอียง.

ฐาน (เท้า) บัญชีแยกประเภทและกรอบวงกบด้านบนจะถูกแนบมากับมาตรฐานแนวตั้งไม่สูงกว่า 450 มิลลิเมตร (18 ") จากด้านล่างของฐาน แผ่นพร้อมกับแผนรั้งเส้นทแยงมุมระหว่างมาตรฐานของอ่าวท้ายที่สุดเพื่อให้แน่ใจว่าอ่าวเป็นรูปสี่เหลี่ยมและเพื่อให้มีเสถียรภาพด้านล่าง

เท่านั้น coupling มุมจะต้องใช้สำหรับการแยกประเภทการเชื่อมต่อมาตรฐาน.

ข้อต่อจะได้รับการติดตั้งเพื่อให้กองกำลังโหลดอยู่บน ด้านคงที่ของ coupler ไม่เคยในด้านสายฟ้า.

ตรวจสอบ (Safety) เพลาจะถูกติดตั้งอยู่ด้านล่างหรือด้านบนเพลาแบกภาระเท่าที่จำเป็นเพื่อป้องกันการลื่นไถล coupler. นี้เป็นสิ่งสำคัญโดยเฉพาะอย่างยิ่งสำหรับโครง underslung และโดยตรงภายใต้หลอดห้อยโหน.

เพลานั่งร้านจะต้องรัดกุม กับ wrenches นั่งร้านเพียง แต่จะแรงบิดตามที่ระบุโดยผู้ผลิต. "บาร์สิบแปดมงกุฎ" จะไม่ถูกนำมาใช้.

ทุกการเชื่อมต่อการมีเพศสัมพันธ์ของยกนั่งร้านจะต้องทำอย่างเต็มที่ปลอดภัยและรัดกุมก่อนการประชุมของลิฟท์ต่อไป
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2025 I Love Translation. All reserved.

E-mail: