Align the powerail sections laterally by sliding the support bolts as desired in the slotted holes of the brackets. (On the EHK bracket, by sliding the supports (1).)
Adjust the height by means of the nuts (G4).
The powerail sections must be precisely aligned to the track and to each other!
Powerail and housing joints for KBSL, KSL, KSLT plants
Above 100 Ampere, you may only use bolted joints!
Risk of damage to the plug-in-joints!
Compress the ends of the plug-in-joints only elastically to avoid any reduction of the elastic force of the spring!
a) Powerail with plug-in-joints
- Compress the plug-in-joints and introduce them in the conductors(G5).
- Push the next powerail section (suspended from sliding hangers) against the first section.
- Compress the plug-in-joints and introduce them partially into the copper conductors (G6).
- Now push the powerail section together (G7).