Example 2
You can even turn an output on within a specified zone. This might be useful for VTEC cam control where you may want an output to turn ON when the RPM is greater than 2000 and stay ON until the engine reaches over 4000 RPM then turn OFF again.
Set the output parameters as follows.
To control a thermo fan set the output mode to 4 (Engine Temp.). If you want the fans to turn ON when the engine temperature is greater than 90°C and turn OFF again when the engine temperature is less than 84°C, the auxiliary output parameters should be set as follows:
Mode 4 (Temp activated relay)
Reverse Acting OFF (Not Ticked.)
ON Above Temp 90 Deg C
ON Below Temp Off
OFF Above Temp Off
OFF Below Temp 84 Deg C
As the engine temperature rises, the output remains OFF until it reaches over 90 degrees, the fans will then turn ON and remain ON until the temperature goes below 84 degrees.
Stinger 4