INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATUL การแปล - INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATUL ไทย วิธีการพูด

INTRODUCTION TO SYSTEM PROTECTION H


INTRODUCTION TO SYSTEM PROTECTION
Hands-On Relay School 2012
CONGRATULATIONS
On choosing the field of system protection. It is an exciting, challenging profession.
System protection has changed considerably in the past 20 years.
Many learning and growth “opportunities” will come your way in the future.
What is System Protection? System protection is the art and science of detecting problems with power system components and isolating these components.
Problems on the power system include: 1. Short circuits 2. Abnormal conditions 3. Equipment failures
NERC defines the protection system as:
Current Approved Definition: Protective relays, associated communication systems, voltage and current sensing devices, station batteries and DC control circuitry.
Purpose of System Protection
• Protect the public • Improve system stability • Minimize damage to equipment • Protect against overloads • Employ relay techs and engineers
What Components (Equipment) Do We Protect?
What Components (Equipment) Do We Protect?
•Generators
•Transformers, Reactors
•Lines
•Buses
•Capacitors
What Components (Equipment) Do We Protect?
Some Basics
Protective relays monitor the current and/or voltage of the power system to detect problems with the power system. Currents and voltages to relays are supplied via CT’s and PT’s.
Some Basics
Current Transformer (CT) A device which transforms the current on the power system from large primary values to safe secondary values. The secondary current will be proportional (as per the ratio) to the primary current.
Some Basics
Potential Transformer (PT) A device which transforms the voltage on the power system from primary values to safe secondary values, in a ratio proportional to the primary value.
What Components (Equipment) Do We Protect?
I. Generator Protection
A. Construction & Theory of Operation
Three Gorges Dam in China Largest in the world (22,000MW, 26 Generators)
What can go wrong?
A. Stator Winding Problems 1. Winding-winding short 2. Stator ground
I. Generator Protection
What can go wrong?
A. Stator Winding Problems
I. Generator Protection
How Do We Protect the Stator? A. Differential Protection (what goes in must come out) 1. Detects phase-phase faults B. Stator Ground Protection 1. 59N (95% of Stator) 2. Third Harmonic Voltage Method (100% of Stator) 3. Signal Injection (100% of Stator)
Generator Protection
Generator Protection
What can go wrong?
B. Rotor Problems 1. Loss of field 2. Field ground a. First ground b. Second ground =TROUBLE
Generator Protection
Rotor
Generator Protection
How Do We Protect the Rotor?
1. Loss of Field a. Impedance
Generator Protection
How Do We Protect the Rotor?
2. Field ground a. DC voltage relay (64F) The field ground relay is connected from the negative side of the field to DC ground. Detects voltage from the field to ground.
Generator Protection
What else can go wrong?
C. Abnormal Conditions 1. Over/Under Frequency 2. Over Excitation 3. Reverse Power 4. Out of Step 5. Unbalance Current
Generator Protection
Transformer Protection
XFMR PROTECTION
Power transformers are expensive, and are a long lead-time item (1 year or longer) so protection must be effective
Transformer Protection
Construction
Construction
Transformer Protection
Construction
Transformer Protection
Transformer size and rating
● MVA: the capacity of the transformer in terms of million volt-amps. Size can range from less than 1 MVA to 500 MVA and higher.
● Transformer rating (MVA) is determined in part by the amount of cooling employed. MVA rating increases with more cooling. OA, FOA (stage 1), FOA (stage 2)
Transformer Protection
What can go wrong?
● Winding-to-winding faults
● Winding-to-ground faults
● Bushing faults
Transformer Protection
Transformer Protection
Protection Methods
● Fuse
● Overcurrent
● Differential
Transformer Protection
High Side Fuse
Transformer Protection
Transformer Damage Curve
Transformer Protection
Overcurrent Relays
Transformer Protection
Differential Protection: What goes in must come out….. P-in = P-out
Transformer Protection
Microprocessor Relays
187T1-T Wraps transformer
187T1-B Wraps transformer and bus
Transformer Protection
187 T1-T Zone of Protection
Transformer Protection
187 T1-B Zone of Protection
Transformer Protection
Some terms you will be learning about this week:
Restraint
Operate
Slope
Inrush
2nd Harmonic
Transformer Protection
LINE PROTECTION
Transmission Line Protection
Transmission lines can vary in length from several hundred feet to several hundred miles, and in voltage (line-to-line) from 46KV to 750KV.
Construction can be simple, such as a single wood pole with insulators atop a crossarm, with little spacing between the conductors and from the conductors to ground. At the other end of the scale are metal lattice structures with bundled conductors (2 or more conductors per phase) with large spacing between conductors and between conductors and ground.
Transmission Line Protection
Transmission Line Protection
Transmission Line Protection
What Can Go Wrong?
FAULTS (Short Circuits)
Some causes of faults: ●Trees ● Lightning ● Animals (birds, squirrels, snakes) ● Weather (wind, snow, ice) ● Natural Disasters (earthquakes, floods) ● Faulty equipment (switches, insulators, clamps, etc.)
Ice Storm
Transmission Line Protection
Transmission Line Protection
Transmission Line Protection
Faults
“Faults come uninvited and seldom go away voluntarily.”
Fault Types:
●Single line-to-ground ● Line-to-line ● Three Phase ● Line-to-line-to-ground
Transmission Line Protection
How Do We Protect Transmission Lines?
A.Overcurrent B.Directional Overcurrent C.Distance (Impedance) D.Pilot 1. DCB (Directional Comparison Blocking 2. POTT (Permissive Overreaching Transfer Trip) E. Line Current Differential
Transmission Line Protection
Overcurrent Protection
Non-Directional Relay responds to overcurrent condition
Instantaneous (IOC) device #50 No intentional time delay
Time Overcurrent (TOC) device #51 Various curve types, including inverse, very inverse, extremely inverse
Transmission Line Protection
Overcurrent Line Protection
Transmission Line Protection
AC Schematic
Time Overcurrent Curves Transmission Line Protection
Transmission Line Protection Directional Overcurrent Protection
Relay responds to overcurrent condition in the forward direction only (device #67, 67N, 67NT)
Will not respond to reverse faults
Compares the current in the line versus a known reference that will always be the same (such as a voltage or polarizing current source)
Transmission Line Protection
Transmission Line Protection
Directional Overcurrent Example
Transmission Line Protection
Distance Protection
A distance relay measures the impedance of a line using the voltage applied to the relay and the current applied to the relay.
When a fault occurs on a line, the current rises significantly and the voltage collapses significantly.
The distance relay (also known as impedance relay) determines the impedance by Z = V/I. If the impedance is within the reach setting of the relay, it will operate.
Transmission Line Protection
Distance Protection
Electromechanical distance relays use torque to restrain or operate KD, GCY, etc. Device #21
Microprocessor distance relays use equations to restrain or operate
SEL, ABB, GE, Areva, etc. Device #11
Transmission Line Protection
Distance Relay CT and PT Connections
Transmission Line Protection
Transmission Line Protection
Distance Protection
Typical zone reach settings
Transmission Line Protection
Distance Protection
When a fault occurs on a transmission line, the current increases and the angle of the current with respect to the voltage changes to a lagging angle, usually between 60 to 85 degrees.
Transmission Line Protection
Distance Protection
The most common characteristic (or protection shape) of distance relays is the mho characteristic, a circular type reach characteristic. Distance relays have a settable maximum torque angle (mta), which is the angle of the current compared to the angle of the voltage at which the relay is most sensitive. In the drawing on the right, the mta is approximately 75 degrees.
Introduction to System Protection
Dependability: the certainty that a protection system will operate when it is supposed to
Security: the certainty that a protection system will not operate when it is not supposed to
Reliability = Dependability + Security
Terminology
Transmission Line Protection
Pilot Relaying Scheme
A protection scheme which employs communications to send a signal from one station to another to allow high speed tripping (permission) or to prevent high speed tripping (blocking).
Pilot protection allows over-reaching zones of protection to ensure full protection of the line as well as high speed tripping.
Transmission Line Protection
Pilot Relaying Scheme

Directional Comparison Blocking (DCB)
A communications based protection scheme where high speed over-reaching tripping is allowed unless a block signal is received.
Transmission Line Protection
Pilot Relaying Scheme

Permissive over-reaching transfer trip (POTT)
A communications based protection scheme where high speed over-reaching tripping is allowed only if a permissive signal is received
Relay
BLOCKING SCHEME OPERATING PRINCIPLE
Relay
STATION “A”
STATION “B”
Transmission Line Protection
BLOCKING SCHEME OPERATING PRINCIPLE
Relay
BLOCKING SCHEME OPERATING PRINCIPLE
BLOCKING SCHEME OPERATING PRINCIPLE
Relay
DO NOT TRIP!!!
External Fault
Transmission Line Protection
BLOCKING SCHEME OPERATING PRINCIPLE
Relay
Internal Fault No block signal is
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably in the past 20 years. Many learning and growth “opportunities” will come your way in the future. What is System Protection? System protection is the art and science of detecting problems with power system components and isolating these components. Problems on the power system include: 1. Short circuits 2. Abnormal conditions 3. Equipment failures NERC defines the protection system as: Current Approved Definition: Protective relays, associated communication systems, voltage and current sensing devices, station batteries and DC control circuitry. Purpose of System Protection • Protect the public • Improve system stability • Minimize damage to equipment • Protect against overloads • Employ relay techs and engineers What Components (Equipment) Do We Protect? What Components (Equipment) Do We Protect? •Generators •Transformers, Reactors •Lines •Buses •Capacitors What Components (Equipment) Do We Protect? Some Basics Protective relays monitor the current and/or voltage of the power system to detect problems with the power system. Currents and voltages to relays are supplied via CT’s and PT’s. Some Basics Current Transformer (CT) A device which transforms the current on the power system from large primary values to safe secondary values. The secondary current will be proportional (as per the ratio) to the primary current. Some Basics Potential Transformer (PT) A device which transforms the voltage on the power system from primary values to safe secondary values, in a ratio proportional to the primary value. What Components (Equipment) Do We Protect? I. Generator Protection A. Construction & Theory of Operation Three Gorges Dam in China Largest in the world (22,000MW, 26 Generators) What can go wrong? A. Stator Winding Problems 1. Winding-winding short 2. Stator ground I. Generator Protection What can go wrong? A. Stator Winding Problems I. Generator Protection How Do We Protect the Stator? A. Differential Protection (what goes in must come out) 1. Detects phase-phase faults B. Stator Ground Protection 1. 59N (95% of Stator) 2. Third Harmonic Voltage Method (100% of Stator) 3. Signal Injection (100% of Stator) Generator Protection Generator Protection What can go wrong? B. Rotor Problems 1. Loss of field 2. Field ground a. First ground b. Second ground =TROUBLE Generator Protection Rotor Generator Protection How Do We Protect the Rotor? 1. Loss of Field a. Impedance Generator Protection How Do We Protect the Rotor? 2. Field ground a. DC voltage relay (64F) The field ground relay is connected from the negative side of the field to DC ground. Detects voltage from the field to ground. Generator Protection What else can go wrong? C. Abnormal Conditions 1. Over/Under Frequency 2. Over Excitation 3. Reverse Power 4. Out of Step 5. Unbalance Current Generator Protection Transformer Protection XFMR PROTECTION Power transformers are expensive, and are a long lead-time item (1 year or longer) so protection must be effective Transformer Protection Construction Construction Transformer Protection Construction Transformer Protection Transformer size and rating ● MVA: the capacity of the transformer in terms of million volt-amps. Size can range from less than 1 MVA to 500 MVA and higher. ● Transformer rating (MVA) is determined in part by the amount of cooling employed. MVA rating increases with more cooling. OA, FOA (stage 1), FOA (stage 2) Transformer Protection What can go wrong? ● Winding-to-winding faults ● Winding-to-ground faults ● Bushing faults Transformer Protection Transformer Protection Protection Methods ● Fuse ● Overcurrent ● Differential Transformer Protection High Side Fuse Transformer Protection Transformer Damage Curve Transformer Protection Overcurrent Relays Transformer Protection Differential Protection: What goes in must come out….. P-in = P-out Transformer Protection Microprocessor Relays 187T1-T Wraps transformer 187T1-B Wraps transformer and bus Transformer Protection 187 T1-T Zone of Protection Transformer Protection 187 T1-B Zone of Protection Transformer Protection Some terms you will be learning about this week: Restraint Operate Slope Inrush 2nd Harmonic Transformer Protection LINE PROTECTION Transmission Line Protection Transmission lines can vary in length from several hundred feet to several hundred miles, and in voltage (line-to-line) from 46KV to 750KV. Construction can be simple, such as a single wood pole with insulators atop a crossarm, with little spacing between the conductors and from the conductors to ground. At the other end of the scale are metal lattice structures with bundled conductors (2 or more conductors per phase) with large spacing between conductors and between conductors and ground. Transmission Line Protection Transmission Line Protection Transmission Line Protection What Can Go Wrong? FAULTS (Short Circuits) Some causes of faults: ●Trees ● Lightning ● Animals (birds, squirrels, snakes) ● Weather (wind, snow, ice) ● Natural Disasters (earthquakes, floods) ● Faulty equipment (switches, insulators, clamps, etc.) Ice Storm Transmission Line Protection Transmission Line Protection Transmission Line Protection Faults “Faults come uninvited and seldom go away voluntarily.” Fault Types: ●Single line-to-ground ● Line-to-line ● Three Phase ● Line-to-line-to-ground Transmission Line Protection How Do We Protect Transmission Lines? A.Overcurrent B.Directional Overcurrent C.Distance (Impedance) D.Pilot 1. DCB (Directional Comparison Blocking 2. POTT (Permissive Overreaching Transfer Trip) E. Line Current Differential Transmission Line Protection Overcurrent Protection Non-Directional Relay responds to overcurrent condition Instantaneous (IOC) device #50 No intentional time delay Time Overcurrent (TOC) device #51 Various curve types, including inverse, very inverse, extremely inverse Transmission Line Protection Overcurrent Line Protection Transmission Line Protection AC Schematic Time Overcurrent Curves Transmission Line Protection Transmission Line Protection Directional Overcurrent Protection Relay responds to overcurrent condition in the forward direction only (device #67, 67N, 67NT) Will not respond to reverse faults Compares the current in the line versus a known reference that will always be the same (such as a voltage or polarizing current source) Transmission Line Protection Transmission Line Protection Directional Overcurrent Example Transmission Line Protection Distance Protection A distance relay measures the impedance of a line using the voltage applied to the relay and the current applied to the relay. When a fault occurs on a line, the current rises significantly and the voltage collapses significantly. The distance relay (also known as impedance relay) determines the impedance by Z = V/I. If the impedance is within the reach setting of the relay, it will operate. Transmission Line Protection
Distance Protection
Electromechanical distance relays use torque to restrain or operate KD, GCY, etc. Device #21
Microprocessor distance relays use equations to restrain or operate
SEL, ABB, GE, Areva, etc. Device #11
Transmission Line Protection
Distance Relay CT and PT Connections
Transmission Line Protection
Transmission Line Protection
Distance Protection
Typical zone reach settings
Transmission Line Protection
Distance Protection
When a fault occurs on a transmission line, the current increases and the angle of the current with respect to the voltage changes to a lagging angle, usually between 60 to 85 degrees.
Transmission Line Protection
Distance Protection
The most common characteristic (or protection shape) of distance relays is the mho characteristic, a circular type reach characteristic. Distance relays have a settable maximum torque angle (mta), which is the angle of the current compared to the angle of the voltage at which the relay is most sensitive. In the drawing on the right, the mta is approximately 75 degrees.
Introduction to System Protection
Dependability: the certainty that a protection system will operate when it is supposed to
Security: the certainty that a protection system will not operate when it is not supposed to
Reliability = Dependability + Security
Terminology
Transmission Line Protection
Pilot Relaying Scheme
A protection scheme which employs communications to send a signal from one station to another to allow high speed tripping (permission) or to prevent high speed tripping (blocking).
Pilot protection allows over-reaching zones of protection to ensure full protection of the line as well as high speed tripping.
Transmission Line Protection
Pilot Relaying Scheme

Directional Comparison Blocking (DCB)
A communications based protection scheme where high speed over-reaching tripping is allowed unless a block signal is received.
Transmission Line Protection
Pilot Relaying Scheme

Permissive over-reaching transfer trip (POTT)
A communications based protection scheme where high speed over-reaching tripping is allowed only if a permissive signal is received
Relay
BLOCKING SCHEME OPERATING PRINCIPLE
Relay
STATION “A”
STATION “B”
Transmission Line Protection
BLOCKING SCHEME OPERATING PRINCIPLE
Relay
BLOCKING SCHEME OPERATING PRINCIPLE
BLOCKING SCHEME OPERATING PRINCIPLE
Relay
DO NOT TRIP!!!
External Fault
Transmission Line Protection
BLOCKING SCHEME OPERATING PRINCIPLE
Relay
Internal Fault No block signal is
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 2:[สำเนา]
คัดลอก!

แนะนำระบบป้องกัน
Hands-On โรงเรียน Relay 2012 ขอแสดงความยินดีในการเลือกด้านการคุ้มครองระบบ มันเป็นที่น่าตื่นเต้นอาชีพที่ท้าทาย. การป้องกันระบบที่มีการเปลี่ยนแปลงอย่างมากในอดีตที่ผ่านมา 20 ปี. การเรียนรู้จำนวนมากและการเติบโตของ "โอกาส" จะมาในแบบของคุณในอนาคต. การป้องกันระบบคืออะไร? การป้องกันระบบเป็นศิลปะและวิทยาศาสตร์ของการตรวจสอบปัญหาเกี่ยวกับส่วนประกอบของระบบไฟฟ้าและการแยกองค์ประกอบเหล่านี้. ปัญหาในระบบไฟฟ้ารวมถึง: 1 วงจรสั้น 2. เงื่อนไขที่ผิดปกติ 3. ความล้มเหลวของอุปกรณ์NERC กำหนดระบบการป้องกันเป็น: ปัจจุบันได้รับการอนุมัติหมาย: ป้องกัน รีเลย์, ระบบการสื่อสารที่เกี่ยวข้องแรงดันไฟฟ้าและอุปกรณ์ตรวจวัดในปัจจุบันแบตเตอรี่สถานีและ DC วงจรควบคุม. วัตถุประสงค์ของการป้องกันระบบ•ปกป้องประชาชน•ปรับปรุงเสถียรภาพของระบบ•ลดความเสียหายต่ออุปกรณ์•ป้องกัน overloads •จ้าง techs รีเลย์และวิศวกรอะไรส่วนประกอบ(อุปกรณ์ ) ไม่ปกป้อง? อะไรส่วนประกอบ (อุปกรณ์) ไม่ปกป้อง? •กำเนิด•หม้อแปลงเครื่องปฏิกรณ์•บรรทัด•รถเมล์•ตัวเก็บประจุส่วนประกอบอะไร(อุปกรณ์) ไม่ปกป้อง? พื้นฐานบางรีเลย์ป้องกันการตรวจสอบในปัจจุบันและ / หรือแรงดันไฟฟ้าของระบบไฟฟ้า ในการตรวจสอบปัญหาเกี่ยวกับระบบไฟฟ้า กระแสและแรงดันไฟฟ้าที่จะรีเลย์มีจำหน่ายผ่านทาง CT และของ PT. บางข้อมูลพื้นฐานเกี่ยวกับหม้อแปลงปัจจุบัน (CT) อุปกรณ์ที่เปลี่ยนในปัจจุบันในระบบพลังงานจากค่าหลักที่มีขนาดใหญ่เป็นค่ารองตู้นิรภัย ปัจจุบันรองจะเป็นสัดส่วน (ตามสัดส่วน) ในปัจจุบันหลัก. บางข้อมูลพื้นฐานเกี่ยวกับศักยภาพหม้อแปลง (PT) อุปกรณ์ที่แปลงแรงดันไฟฟ้าในระบบไฟฟ้าจากค่าหลักเป็นค่ารองปลอดภัยในสัดส่วนอัตราส่วนค่าหลัก . สิ่งที่ส่วนประกอบ (อุปกรณ์) ไม่ปกป้องเรา? ครั้งที่หนึ่ง คุ้มครองกำเนิดเอ ก่อสร้างและทฤษฎีของการดำเนินงานสามโตรกเขื่อนในประเทศจีนที่ใหญ่ที่สุดในโลก (22,000MW 26 เครื่องกำเนิดไฟฟ้า) สิ่งที่สามารถไปอย่างผิดปกติ? A. สเตเตอร์คดเคี้ยวปัญหา 1. ม้วนขดลวดสเตเตอร์สั้น 2. พื้นดินครั้งที่หนึ่ง คุ้มครองกำเนิดสิ่งที่สามารถไปอย่างผิดปกติ? A. สเตเตอร์คดเคี้ยวปัญหาครั้งที่หนึ่ง คุ้มครองกำเนิดอย่าวิธีปกป้องสเตเตอร์หรือไม่? A. คุ้มครองที่แตกต่างกัน (สิ่งที่จะไปจะต้องออกมา) 1. ตรวจพบความผิดพลาดเฟสเฟสบีสเตเตอร์พื้นคุ้มครอง 1. 59N (95% ของสเตเตอร์) 2. วิธีที่สามแรงดันฮาร์มอนิ (100% ของสเตเตอร์) 3. สัญญาณฉีด ( 100% ของสเตเตอร์) เครื่องกำเนิดไฟฟ้าคุ้มครองคุ้มครองกำเนิดสิ่งที่สามารถไปอย่างผิดปกติ? บี ปัญหาโรเตอร์ 1. การสูญเสียของสนาม 2. พื้นสนาม ขพื้นดินครั้งแรก พื้นดินที่สอง = TROUBLE Generator คุ้มครองโรเตอร์คุ้มครองGenerator ทำวิธีปกป้องโรเตอร์หรือไม่1 การสูญเสียของสนาม ความต้านทานการป้องกันเครื่องกำเนิดไฟฟ้าวิธีทำเราปกป้องโรเตอร์หรือไม่2 สนามพื้นดิน ถ่ายทอดแรงดันไฟฟ้ากระแสตรง (64F) สนามถ่ายทอดพื้นดินที่เชื่อมต่อจากด้านลบของสนามพื้นดินดีซี ตรวจจับแรงดันไฟฟ้าจากสนามกับพื้น. Generator คุ้มครองอะไรที่สามารถไปอย่างผิดปกติ? ซี สภาพผิดปกติ 1. สูง / ต่ำกว่าความถี่ 2. กระตุ้น 3. ไฟฟ้า 4. ย้อนกลับออกมาจากขั้นตอนที่ 5 ไม่สมดุลปัจจุบันGenerator คุ้มครองคุ้มครองหม้อแปลงXFMR ป้องกันหม้อแปลงไฟฟ้าที่มีราคาแพงและเป็นรายการที่เวลานำยาว(1 ปีหรือนานกว่านั้น) การป้องกันจึงต้องมีประสิทธิภาพหม้อแปลงคุ้มครองก่อสร้างก่อสร้างหม้อแปลงคุ้มครองก่อสร้างคุ้มครองหม้อแปลงขนาดหม้อแปลงและการจัดอันดับ● MVA: ความจุของหม้อแปลงในแง่ของล้านโวลต์แอมป์ ขนาดได้ตั้งแต่น้อยกว่า 1 MVA 500 ​​MVA และสูงกว่า. ●คะแนนหม้อแปลง (MVA) จะถูกกำหนดในส่วนของจำนวนเงินของการทำความเย็นที่ใช้ MVA การเพิ่มขึ้นของการระบายความร้อนที่มีคะแนนมากขึ้น โอเอ FOA (ระยะที่ 1) FOA (ระยะที่ 2) การป้องกันหม้อแปลงสิ่งที่สามารถไปอย่างผิดปกติ? ●ม้วนไปม้วนผิดพลาด●คดเคี้ยวสู่พื้นดินความผิดพลาดความผิดพลาดของปลอก●หม้อแปลงคุ้มครองคุ้มครองหม้อแปลงวิธีการป้องกัน●ฟิวส์●สภาวะกระแสไฟเกิน●ความแตกต่างของหม้อแปลงคุ้มครองสูงด้านฟิวส์หม้อแปลงคุ้มครองหม้อแปลงความเสียหายCurve หม้อแปลงคุ้มครองสภาวะกระแสไฟเกินรีเลย์หม้อแปลงคุ้มครองคุ้มครองที่แตกต่างกัน: อะไรไปจะต้องออกมา ... .. P-ใน = P-ออกหม้อแปลงคุ้มครองรีเลย์ไมโคร187T1-T ห่อหม้อแปลงหม้อแปลง187T1-B ห่อและรถบัสหม้อแปลงคุ้มครอง187 T1-T โซนคุ้มครองหม้อแปลงคุ้มครอง187 T1-B โซนคุ้มครองคุ้มครองหม้อแปลงเงื่อนไขบางอย่างที่คุณจะได้เรียนรู้เกี่ยวกับในสัปดาห์นี้: ยับยั้งชั่งใจงานลาดไหลเข้า2 ฮาร์มอนิหม้อแปลงคุ้มครองสายป้องกันการส่งผ่านสายการป้องกันสายส่งสามารถแตกต่างกันในความยาวจากหลายร้อยฟุตไปหลายร้อยไมล์และแรงดันไฟฟ้า (สายไปสาย) จาก 46KV เพื่อ 750kV. ก่อสร้างได้ง่ายเช่นเสาไม้เดียวที่มีฉนวนบนคอนที่มีระยะห่างระหว่างตัวนำและจากตัวนำ ลงไปที่พื้น ที่ปลายอีกด้านของขนาดมีโครงสร้างตาข่ายโลหะที่มีตัวนำแถมมา (2 หรือตัวนำต่อเฟส) ที่มีระยะห่างขนาดใหญ่ระหว่างตัวนำและระหว่างตัวนำและพื้นดิน. ส่งสายการป้องกันการส่งผ่านสายการป้องกันการส่งผ่านสายการป้องกันสิ่งที่สามารถไปผิด? ข้อบกพร่อง (สั้น วงจร) สาเหตุบางส่วนของความผิดพลาด: ●●ฟ้าผ่าต้นไม้●สัตว์ (นกกระรอกงู) ●อากาศ (ลมหิมะน้ำแข็ง) ●ภัยพิบัติทางธรรมชาติ (แผ่นดินไหว, น้ำท่วม) ●อุปกรณ์ผิดพลาด (สวิทช์, ฉนวน, ที่หนีบ ฯลฯ ) พายุน้ำแข็งส่งสายการป้องกันการป้องกันสายส่งส่งสายการป้องกันความผิดพลาด"ผิดพลาดมาไม่ได้รับเชิญและไม่ค่อยหายไปโดยสมัครใจ." ประเภทความผิดพลาด: ●เดี่ยวสายลงดิน●สายไปยังบรรทัด●สามเฟส●สายต่อสายไป -ground การป้องกันสายส่งทำอย่างไรเราป้องกันสายส่ง? A.Overcurrent B.Directional สภาวะกระแสไฟเกิน C.Distance (ความต้านทาน) D.Pilot 1. DCB (เปรียบเทียบทิศทางการปิดกั้น 2. Pott (การโอนอนุญาต overreaching การเดินทาง) อีสายที่แตกต่างกันในปัจจุบันส่งสายคุ้มครองป้องกันกระแสเกินที่ไม่ใช่ทิศทางรีเลย์ตอบสนองต่อกระแสเกินสภาพทันที(IOC) อุปกรณ์ # 50 ไม่มีเวลาเจตนาล่าช้าเวลาสภาวะกระแสไฟเกิน(TOC) อุปกรณ์ # 51 ชนิดโค้งต่างๆรวมทั้งผกผันมากผกผันผกผันมากส่งสายคุ้มครองสภาวะกระแสไฟเกินสายการป้องกันการส่งผ่านสายคุ้มครองAC แผนผังเวลาสภาวะกระแสไฟเกินCurves ส่งสายการป้องกันการส่งผ่านสายคุ้มครองทิศทางสภาวะกระแสไฟเกินการป้องกันการถ่ายทอดตอบสนองต่อกระแสเกินเงื่อนไขในทิศทางที่ไปข้างหน้าเท่านั้น(อุปกรณ์ # 67, 67N, 67NT) จะไม่ตอบสนองต่อการกลับผิดพลาดเปรียบเทียบปัจจุบันในสายเมื่อเทียบกับที่รู้จักกันการอ้างอิงที่มักจะเหมือนกัน (เช่นแรงดันไฟฟ้าหรือแหล่งที่มาในปัจจุบันขั้ว) ส่งสายการป้องกันการส่งผ่านสายคุ้มครองทิศทางสภาวะกระแสไฟเกินตัวอย่างส่งสายคุ้มครองระยะคุ้มครองมาตรการรีเลย์ระยะทางความต้านทานของสายโดยใช้แรงดันไฟฟ้าที่ใช้กับการถ่ายทอดและในปัจจุบันนำไปใช้กับการถ่ายทอด. เมื่อมีความผิดพลาดเกิดขึ้นในสายที่เพิ่มขึ้นอย่างมีนัยสำคัญในปัจจุบันและแรงดันไฟฟ้าอย่างมีนัยสำคัญยุบ. รีเลย์ระยะทาง (หรือที่เรียกว่าการถ่ายทอดความต้านทาน) กำหนดความต้านทานโดย Z = V / I ถ้าความต้านทานอยู่ในการตั้งค่าการเข้าถึงของการถ่ายทอดก็จะดำเนินการ. ส่งสายคุ้มครองระยะคุ้มครองระบบเครื่องกลไฟฟ้ารีเลย์ระยะทางใช้แรงบิดที่จะยับยั้งหรือดำเนินการKD, GCY ฯลฯ อุปกรณ์ # 21 ไมโครรีเลย์ระยะทางใช้สมการที่จะยับยั้งหรือดำเนินการSEL, ABB, GE, Areva ฯลฯ อุปกรณ์ # 11 ส่งสายคุ้มครองระยะทาง Relay CT และ PT การเชื่อมต่อการส่งผ่านสายการป้องกันการส่งผ่านสายคุ้มครองระยะคุ้มครองโซนทั่วไปเข้าถึงการตั้งค่าการส่งผ่านสายการปกป้องคุ้มครองระยะทางเมื่อมีความผิดพลาดเกิดขึ้นบนสายส่งที่เพิ่มขึ้นในปัจจุบันและมุมของปัจจุบันที่เกี่ยวกับการเปลี่ยนแปลงของแรงดันไฟฟ้าไปยังมุมปกคลุมด้วยวัตถุฉนวนที่ปกติจะอยู่ระหว่าง 60-85 องศา. ส่งสายคุ้มครองระยะคุ้มครองลักษณะที่พบมากที่สุด(หรือรูปร่างป้องกัน) ของรีเลย์ระยะทางลักษณะกระแสไฟฟ้าชนิดกลมถึงลักษณะ . รีเลย์ระยะทางมีมุมที่แรงบิดสูงสุดตัวอย่างไฟล์ (MTA) ซึ่งเป็นมุมในปัจจุบันเมื่อเทียบกับมุมของแรงดันไฟฟ้าที่ถ่ายทอดที่มีความสำคัญมากที่สุด ในการวาดภาพทางด้านขวา, เอ็มทีจะอยู่ที่ประมาณ 75 องศา. รู้เบื้องต้นเกี่ยวกับการป้องกันระบบDependability: ความมั่นใจว่าระบบการป้องกันจะทำงานเมื่อมันควรจะรักษาความปลอดภัย: ความมั่นใจว่าระบบการป้องกันจะไม่ทำงานเมื่อมันไม่ควรจะความน่าเชื่อถือ = Dependability + การรักษาความปลอดภัยศัพท์ส่งสายคุ้มครองนักบินRelaying โครงการโครงการการป้องกันซึ่งมีพนักงานสื่อสารการส่งสัญญาณจากสถานีหนึ่งไปยังอีกที่จะอนุญาตให้สะดุดด้วยความเร็วสูง(สิทธิ์) หรือเพื่อป้องกันไม่ให้สะดุดความเร็วสูง (แบบปิดกั้น). ป้องกันนักบินช่วยให้เกิน ถึงโซนของการป้องกันเพื่อให้แน่ใจว่าคุ้มครองเต็มรูปแบบของสายเช่นเดียวกับการสะดุดด้วยความเร็วสูง. ส่งสายคุ้มครองนักบิน Relaying โครงการเปรียบเทียบทิศทางการปิดกั้น(DCB) การสื่อสารโครงการการป้องกันโดยที่ความเร็วสูงกว่าถึงทริปที่ได้รับอนุญาตเว้นแต่สัญญาณบล็อกที่ได้รับ . ส่งสายคุ้มครองนักบิน Relaying โครงการอนุญาตมากกว่าถึงรถรับส่ง(Pott) การสื่อสารโครงการการป้องกันโดยที่ความเร็วสูงกว่าถึงทริปที่ได้รับอนุญาตเฉพาะในกรณีที่สัญญาณอนุญาตที่ได้รับการถ่ายทอดการปิดกั้นโครงการปฏิบัติการหลักการRelay STATION "A" สถานี "บี "การป้องกันสายส่งการปิดกั้นการดำเนินงานโครงการหลักการRelay การปิดกั้นการดำเนินงานโครงการหลักการการปิดกั้นการดำเนินงานโครงการหลักการRelay ไม่เที่ยว !!! ภายนอกผิดพลาดส่งสายการป้องกันการปิดกั้นการดำเนินงานโครงการหลักการรีเลย์ภายในบล็อกสัญญาณความผิดปกติไม่มี

































































































































































































การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 3:[สำเนา]
คัดลอก!


แนะนำมือป้องกันระบบถ่ายทอดโรงเรียน 2012
ยินดีด้วย
เลือกฟิลด์การป้องกันระบบ มันเป็นที่น่าตื่นเต้น ท้าทาย อาชีพ การป้องกัน
ระบบมีการเปลี่ยนแปลงมากในรอบ 20 ปี
การเรียนรู้มากมาย และการเจริญเติบโตของ " โอกาส " จะมาวิธีการของคุณในอนาคต
สิ่งที่ระบบป้องกัน ?ระบบป้องกันเป็นศิลปะและวิทยาศาสตร์ของการตรวจสอบปัญหาระบบไฟฟ้ากำลัง ส่วนประกอบ และการแยกองค์ประกอบเหล่านี้
ปัญหาระบบพลังงาน ได้แก่ 1 . สั้นวงจร 2 ความผิดปกติของภาพ 3 อุปกรณ์ล้มเหลว
nerc กำหนดระบบป้องกัน :
ปัจจุบันอนุมัตินิยาม : รีเลย์ป้องกันที่เกี่ยวข้องการสื่อสารระบบการตรวจจับแรงดันและกระแสของอุปกรณ์แบตเตอรี่สถานี และวงจรควบคุม DC
-
วัตถุประสงค์ของการป้องกันระบบป้องกัน - ปรับปรุงระบบบริการประชาชน เสถียรภาพ ลดความเสียหายของอุปกรณ์ป้องกันแต่ละ overloads จ้างบริการถ่ายทอดเทคนิคและวิศวกร
สิ่งที่ส่วนประกอบ ( อุปกรณ์ ) เราปกป้อง
สิ่งที่ส่วนประกอบ ( อุปกรณ์ ) เราปกป้อง
-
- หม้อแปลงไฟฟ้า เตาปฏิกรณ์
-
-
- สายรถเมล์ /
อะไรองค์ประกอบ ( อุปกรณ์ ) เราปกป้อง

รีเลย์ป้องกันพื้นฐานบางอย่างตรวจสอบในปัจจุบันและ / หรือแรงดันไฟฟ้าของระบบพลังงานเพื่อตรวจหาปัญหากับระบบพลังงาน กระแสและแรงดันไฟฟ้า เพื่อถ่ายทอดให้ผ่านผล CT และ PT .

ปัจจุบันพื้นฐานหม้อแปลง ( CT ) เป็นอุปกรณ์ที่แปลงในปัจจุบันในระบบไฟฟ้ากำลัง จากค่าหลักใหญ่ค่ารองปลอดภัยกระแสรองจะได้สัดส่วน ( ตามอัตราส่วน ) หลักในปัจจุบัน

บางพื้นฐานศักยภาพหม้อแปลง ( PT ) เป็นอุปกรณ์ที่แปลงแรงดันในระบบไฟฟ้ากำลัง จากค่านิยมหลักค่ารองปลอดภัย ในอัตราส่วน สัดส่วนของมูลค่าหลัก
สิ่งที่ส่วนประกอบ ( อุปกรณ์ ) เราปกป้อง

. . &การป้องกันเครื่องกำเนิดไฟฟ้าสร้างทฤษฎี ปฏิบัติการ
สามโตรกเขื่อนในประเทศจีนที่ใหญ่ที่สุดในโลก ( 22000mw 26 เครื่อง )
สิ่งที่สามารถไปผิด
a ปัญหาขดลวดสเตเตอร์ 1 เลี้ยวลดคดเคี้ยวสั้น 2 สเตเตอร์พื้นดิน
.
เครื่องป้องกันสิ่งที่สามารถไปผิด
a ขดลวดสเตเตอร์ที่มาปัญหา

แล้วเราจะปกป้องคุ้มครองฉันผลิตสเตเตอร์ ? 1 . ค่าป้องกัน ( ที่เข้าไปแล้วต้องออกมา ) ตรวจจับเฟสเฟสผิดพ.
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2025 I Love Translation. All reserved.

E-mail: