The 12 buildings for use as a hotel under Article 10 shall be equipped with fire extinguishers in accordance with the following.
(1) The nature of the flat, a townhouse or semi-detached house. With a height of no more than two classes. To install fire extinguishers cell types and sizes to suit the condition of buildings and building materials within 1 percent.
(2) building other than a building under subsection (1) shall be equipped with hand-held fire extinguisher on each floor, 1 unit per floor area not exceeding 1,000 square meters of any distance up to 45 meters, but not less than 1 unit per floor.
(3) the installation of fire extinguishers. Must be installed to the top of the machine from the floor up to 1.50 meters and must be installed in a place where they can see and read the information available from the hotel.
(4) fire extinguisher must be in use at any time and can be implemented easily.