– Strobe Synchronization for System Sensor, Wheelock,
Gentex, Faraday, or Amseco devices.
– Selective Silence (horn-strobe mute).
– Temporal or Steady Signal.
– Silenceable or Nonsilenceable.
• Optional N-CAC-5X Style Z (Class A) Converter Module for
NACs and IDCs (2 required for SFP-10UD).
• Form-C Relays for Alarm, Trouble and Supervisory - Contact
Ratings 2.0 A@ 30 VDC or 30 VAC (resistive).
• 3.0 A total system current for SFP-5UD.
• 7.0 A total system current for SFP-10UD.
• Optional Dress Panel DP-51050 (red)
• Optional Dress Panel DP-51050B (black).
• Optional Trim Ring TR-CE/-B for semi-flush mounting.
• 24 volt operation.
• Low AC voltage sense.
• Alarm Verification.
• PAS (Positive Alarm Sequence).
• Automatic battery trickle charger.
• Up to eight ANN-BUS annunciators:
– Optional 8 zone Relay Module N-ANN-RLY.
– Optional LED Annunciator Module N-ANN-LED,
– Optional Remote LCD Annunciator N-ANN-80.
– Optional Remote Printer Gateway N-ANN-S/PG.
– Optional LED Annunciator Driver N-ANN-I/O.
• Optional 4XTM module (conventional reverse polarity/city
box transmitter).