3 Specification : PVC insulated (THW), (60227 IEC01)
(1) Reference to Contract Document : New Item
Reason of Revision : Missing from the Specification
PVC insulated (THW), (60227 IEC01)
(2) The cables shall be annealed copper solid or stranded wire with heat resistant
polyvinyl chloride (PVC) insulation material, which has rated not more than
450/750V 70°C compliance with TIS 11-2553 Part 3 Table 1&2
(3) All cable size 6 mm2 or lager shall be stranded.
(4) Cables wiring inside the luminaries shall not be smaller than 1.0 mm²
specified on the Drawings.
(5) Control wires size shall not be smaller than 1.5 mm²
Cable wiring to the general purposed outlets shall not be smaller than 2.5 mm²
or as specified on the Drawings or Panel Board Schedules.