● 0: Given by panel potentiometer. Set the frequency by adjusting the operating panel's potentiometer
● 1: Given by panel digital setting. Use the value of parameter [b1.04] as the set frequency. Use ▼ and ▲ keys to change the output frequency value when the frequency converter is running. See descriptions for [b1.01].
● 2: Given by external analog AIV Set the frequency by external analog voltage input. The input resistance is 40 kΩ. Please also set parameters [E0.10] ~ [E0.28].
● 3: Given by external analog AIC Set the frequency by external analog current input. The input resistance is 499 Ω. Please also set parameters [E0.10] ~ [E0.28].
● 4: Set by external UP / DOWN terminals In this mode, the output frequency can be adjusted easily with the UP, DOWN and RESET terminals. For details, please see parameters [S3.32] and [S3.33].
● 5: Given via communication Set output frequency by communication with an external computer or PLC. For relevant settings, please refer to parameters in group H.
● 6: Given by multi-speed.–Set [b1.00]=6–When RUN / STOP command source is from panel, any 3 of parameters [E0.01] ~ [E0.05] need to be set as: one to 1 "Multi-speed control terminal 1", one to 2 "Multi-speed control terminal 2" and one to 3 "Multi-speed control terminal 3". Acceleration / deceleration time and rotation direction can be defined by multispeed / PLC configuration (See parameters [E2.35] ~ [E2.50]). 5