operating voltage and 40 MW load. A self excited
overvoltage test at 72 Hz resulted in another failure. At this
point the manufacturer performed impulse tests on all
remaining coils in the machine resulting in 63 additional
turn failures. This was in addition to the 20 that had
occurred while the unit was self excited.