The Count Down instruction that counts down by one every time the preceding logic transitions from false to true. The Counter.DN bit is set when the Accumulator reaches the Preset. The accumulator will continue to count even when the done bit is set. The CTD instruction can be paired with a CTU instruction referencing the same tag name. The overflow and underflow bits are set when the Accumulator exceeds the upper or lower limits.