1) the calculation still using the old material aluminium composite NOT aluminium? The aluminium is supposed more heavy than aluminium composite .... Please clarify
2) the calculation now is still using the closure design, the latest design has less strips. Therefore the force calculation should be different?
3) the calculation seems there but they didn't indicate the force calculation by each strip
4) the force calculation from the nut to the frame & onto facades didn't indicate clearly .. So how the nut nailed into wall & structure supporting the steel frame & facade strips have not clearly mentioned ??
5) please review all RED REMARKS made by MAXZ & looking forward to having detail reply ASAP for decision
Please clarify with me anytime for any uncertain points