2 Ageing test methodology
As mentioned before, the ageing test methodology was
outlined in an earlier publication [29] and briefly mentioned
here for clarity. Basically, the methodology consists of three
cycle sequences: the first one is to stress the insulation for a
period of 24 h in a salt-fog chamber, followed by a 12 h
dry period with UV. Finally, after switching off the UV,
24 h of clean fog is applied; for a total time of 60 h per
cycle. The test sequence is given in Table 1. Then, the
cycle is repeated for a total time of 5000 h with
the components continuously energised at nominal phaseto-
ground voltage and 60 Hz.
Before starting the ageing test, the insulations are washed
off and then a pollution layer is deposited on their
insulation surface by using the solid layer method. Slurry is
prepared with 20 g of kaolin and 10 g of salt per 50 ml of
demineralised water. A sponge is used to apply the slurry
by hand. At the half-way through the test, namely, after
2500 h of testing, the insulations are washed off again and
after that, the pollutant layer is reapplied. After applying the
new pollutant layer on the insulation surface, the apparatus
is allowed to rest for 48 h prior to restarting the test,
thereby allowing the contaminant layer to dry and to
recover hydrophobicity.
During the ageing test, the leakage current is measured; the
frequency and range of the leakage current peaks are recorded
and classified by a custom-made data acquisition system [30].
The current peak measured is the highest value at each
semi-cycle of the 60 Hz signal. The electric field is also
measured before the test and again at 2500 and 5000 h with
a composite insulator tester developed by Hydro-Que´bec.
These results may also be used to determine whether the
insulator becomes defective during the test [2, 4, 31]. Five
thousand hours after the test was ended, another electric
field measurement was performed on one sample, in order
to validate the obtained results. Corona observations are
also made at 2500, 3260 and 5000 h, with a DayCor II
corona camera developed by EPRI Solutions, which helps
to identify possible damage in the insulation [2, 4, 32].
At several times during the test, the static contact angle and
a microstructure analysis of the insulating surface of each
specimen is carried out. Digital imaging analysis is used to
measure the contact angle. The microstructure analysis is
done by applying the replica technique, a technique used in
metallurgy.
2 Ageing test methodology
As mentioned before, the ageing test methodology was
outlined in an earlier publication [29] and briefly mentioned
here for clarity. Basically, the methodology consists of three
cycle sequences: the first one is to stress the insulation for a
period of 24 h in a salt-fog chamber, followed by a 12 h
dry period with UV. Finally, after switching off the UV,
24 h of clean fog is applied; for a total time of 60 h per
cycle. The test sequence is given in Table 1. Then, the
cycle is repeated for a total time of 5000 h with
the components continuously energised at nominal phaseto-
ground voltage and 60 Hz.
Before starting the ageing test, the insulations are washed
off and then a pollution layer is deposited on their
insulation surface by using the solid layer method. Slurry is
prepared with 20 g of kaolin and 10 g of salt per 50 ml of
demineralised water. A sponge is used to apply the slurry
by hand. At the half-way through the test, namely, after
2500 h of testing, the insulations are washed off again and
after that, the pollutant layer is reapplied. After applying the
new pollutant layer on the insulation surface, the apparatus
is allowed to rest for 48 h prior to restarting the test,
thereby allowing the contaminant layer to dry and to
recover hydrophobicity.
During the ageing test, the leakage current is measured; the
frequency and range of the leakage current peaks are recorded
and classified by a custom-made data acquisition system [30].
The current peak measured is the highest value at each
semi-cycle of the 60 Hz signal. The electric field is also
measured before the test and again at 2500 and 5000 h with
a composite insulator tester developed by Hydro-Que´bec.
These results may also be used to determine whether the
insulator becomes defective during the test [2, 4, 31]. Five
thousand hours after the test was ended, another electric
field measurement was performed on one sample, in order
to validate the obtained results. Corona observations are
also made at 2500, 3260 and 5000 h, with a DayCor II
corona camera developed by EPRI Solutions, which helps
to identify possible damage in the insulation [2, 4, 32].
At several times during the test, the static contact angle and
a microstructure analysis of the insulating surface of each
specimen is carried out. Digital imaging analysis is used to
measure the contact angle. The microstructure analysis is
done by applying the replica technique, a technique used in
metallurgy.
การแปล กรุณารอสักครู่..

2 ริ้วรอย
ทดสอบวิธีการดังกล่าวก่อนที่จะ อายุทดสอบวิธีการศึกษา
อธิบายไว้ในก่อนหน้านี้สิ่งพิมพ์ [ 29 ] และเอ่ยถึง
ที่นี่เพื่อความชัดเจน โดยทั่วไป วิธีการศึกษาประกอบด้วยสาม
รอบลำดับ : หนึ่งคือความเครียด ฉนวนกันความร้อนสำหรับ
ระยะเวลา 24 ชั่วโมงในหมอกเกลือ ห้อง ตามด้วย 12 H
ระยะเวลาแห้งด้วยแสงยูวี ในที่สุด หลังจากปิด UV
24 ชั่วโมงของหมอกที่สะอาดใช้ เพราะเวลารวม 60 ชั่วโมงต่อ
รอบ ทดสอบลำดับให้ตารางที่ 1 งั้น
รอบซ้ำสำหรับรวมเวลา 5 ชั่วโมง
ส่วนประกอบที่ระบุ phaseto มีพลังอย่างต่อเนื่อง -
พื้นแรงดัน 60 Hz .
ก่อนที่จะเริ่มขบวนการทดสอบ ฉนวนจะถูกล้างออกแล้วเป็นมลพิษ
ฝากบนของชั้น คือฉนวนกันความร้อนที่พื้นผิวโดยใช้วิธีชั้นแข็ง สารละลายคือ
เตรียม 20 กรัมและ 10 กรัมของเกลือต่อดินขาว
demineralised 50 มล. ของน้ำ ฟองน้ำที่ใช้ทาสารละลาย
ด้วยมือ ที่ครึ่งทางผ่านทดสอบ ได้แก่ การทดสอบหลังจาก
2 H , ฉนวนจะล้างออกอีกครั้งและ
หลังจากนั้นมลพิษเป็นชั้นนํามาใช้อีก . หลังจากใช้
ชั้นมลพิษใหม่บนพื้นผิวฉนวนอุปกรณ์
จะได้รับอนุญาตให้พัก 48 ชั่วโมงก่อนที่จะเริ่มการทดสอบ
เพื่ออนุญาตให้เสมอชั้นแห้งและหายไม่ชอบ
.
ในระหว่างอายุการทดสอบการรั่วไหลในปัจจุบันเป็นวัด ;
ความถี่และช่วงของการรั่วไหลในปัจจุบันยอดบันทึก
และ จำแนกตามระบบข้อมูลลูกค้า [ 30 ] .
ปัจจุบันวัดเป็นยอดสูงสุดในแต่ละรอบของ 60 Hz
กึ่งสัญญาณ สนามไฟฟ้าก็
วัดก่อนการทดสอบ และอีกครั้งที่ 2500 และ 5000 ชั่วโมง
ประกอบฉนวนทดสอบที่พัฒนาโดยไฮโดรคิวใหม่ บีอีซี .
ผลลัพธ์เหล่านี้อาจจะใช้เพื่อตรวจสอบว่า
ฉนวนจะบกพร่องในการสอบ [ 2 , 4 , 5 ] 5
พันชั่วโมงหลังจากการทดสอบสิ้นสุดอีกแบบคือใช้สนามไฟฟ้า
ตัวอย่างหนึ่งเพื่อตรวจสอบผลการทดลอง โคโรน่าการสังเกตเป็น
ยังทำที่ 3260 2500 และ 5000 ชั่วโมง กับ daycor II
โคโรน่ากล้องพัฒนาโดย epri โซลูชั่นซึ่งจะช่วย
ระบุเป็นไปได้ความเสียหายในฉนวน [ 2 , 4 , 32 ] .
ที่หลายครั้งในระหว่างการทดสอบแบบสถิตและ
มุมสัมผัสเป็นโครงสร้างจุลภาคการวิเคราะห์ของฉนวนพื้นผิวของแต่ละ
ตัวอย่างคือการ การวิเคราะห์ภาพดิจิตอลใช้
วัดมุมสัมผัส การวิเคราะห์โครงสร้างจุลภาคเป็น
ทำโดยใช้เทคนิคจำลอง , เทคนิคที่ใช้ใน
โลหะการ
การแปล กรุณารอสักครู่..