Based on the specific consumption it can be determined the
maximum allowable loading for half an hour for a MV line of
distribution network. The maximum loading reached is 74%
with a rate of use for 0.95 and 0.93 of the equipment. This
values show that the loading is crossing the maximal
admissible loading with 14%. The determined value shows a
probability to defect of the line. Therefore to decrease the
loading of the line becomes a necessity. Using the VPP, the
loading will decrease as shown in section III. For the
calculation of the stability parameters it is chosen as an average
value of 60 receivers for a MV/LV transformer.