The rectifier charger shall be capable of supplying full-rated, regulated DC power
without the batteries connected. When operating without the battery, the system
shall meet all specified performance requirements except reserve time and ripple
voltage. With the battery disconnected, maximum ripple voltage shall not exceed
5%. The design shall be such that it is possible to connected and disconnected to
the battery charger while supply power to load.