Storage of Powered Materials Handling Equipment. Battery, gasoline, LP, CNG, or diesel-powered equipment may be stored in a magazine, storehouse or other suitable location that contains only non-explosives materials. Keep equipment at least 10 feet from combustible material. Keep aisles clear at all times and space to minimize spread of fire from one unit to another. Equipment essential to day-to-day operations may be parked in fire-resistive buildings containing explosives. The following minimum requirements must be met:
8.35.1. Use properly rated fire walls and closed doors to completely separate equipment from bays, rooms or cubicles containing explosives.
8.35.2. Ensure designed fire-resistant ratings for the enclosures containing explosives are not degraded.
8.35.3. Battery charging must comply with AFOSH Standard 91-66.
8.35.4. Weapons safety and fire protection personnel must review the local situation for any additional measures necessary to enhance safety.