We noted that the Generators #1 to 3 are installed with circuit breakers setting of 630A and
appears to exceed 15% above the full-load rating of the Generators (437A).
Please be advised that the generator are to be provided with the following trip settings:
1) Instantaneous Trip
2) Short-time overcurrent trips
3) Reverse power protection
Please refer to 4-6-2/9.3.2 & 4-6-2/9.5 of ABS Steel Vessels Rules.
Please clarify the settings.