Heat runs
Oden AT is ideal for performing heat runs. Current can be applied
continuously or through programmable intervals. The times can be
shown in minutes and hours which facilitates long-term testing.
Automatic reclosers and sectionalizers
Oden AT can also be set to test direct-acting automatic reclosers and
sectionalizers. Operating limits, partial times, total times and the
number of operations before lockout can be measured. Userselectable
reclosing sequences can be programmed for testing
sectionalizers.
Testing integrity of ground grids
and safety-ground devices
One way to test ground grids is by injecting current between a
reference ground and the ground to be tested and measuring the
voltage drop and the percentage of current flowing through the
ground grid. The type X current unit included with Oden AT is designed
for this type of application. Personal safety grounds must be tested at
rated current, a task for which Oden AT is well suited.