turbine startup and shutdown procedure
turbine startup procedure
1.A minimum duration of 4 hours before turbine operation, the auxiliary lubrication oil pump M-139 should be selected to AUTO, the pump will automatically start. Ensure the oil tank ventilation fan M-134 is selected to AUTO, the fan will automatically start when the auxiliary oil pump is runing The emergency lubrication oil pump M-135 should be selected to AUTO after the auxiliary pump is runing. (Press the reset button before selecting the emergency lubrication oil pump to auto control.)