A directional power relay function (32) is used in peak-shaving
and load-flowing DG applications where the DG is operated to
supply only a portion of the local load at the installation and there
is no intent to sell power back to the utility. The directional power
relay is used to enforce the contract that states that no power will
flow to the utility.