A similar relationship can be derived for the reactive power Q and terminal voltage
VT. When adding a lagging load to a synchronous generator, its terminal voltage
decreases. When adding a leading load to a synchronous generator, its terminal
voltage increases.
The plot of terminal voltage vs.
reactive power is not necessarily
linear.
Both the frequency-power and
terminal voltage vs. reactive power
characteristics are important for
parallel operations of generators.
When a generator is operating alone supplying the load:
1.The real and reactive powers are the amounts demanded by the load.
2.The governor of the generator controls the operating frequency of the system.
3.The field current controls the terminal voltage of the power system.