For analysing the performance of system water load is considered. Water at 26.6˚C was filled in the container
before switching ON the system. The temperature reading is taken out at every 30 minute interval and was tabulated.
The readings were repeated until we get the least possible steady temperature. Even though the system is mainly designed for maintaining a fixed temperature, the above experiment was
conducted to ensure that the system can be adapted for sensible cooling also. The steady temperature attained was
13˚C. It took almost thirteen hours to attain the same from ambient conditions. The cabin temperature drop was at an
average rate of 1.06°C/hr.