CompMax sets a maximum limit on the time between
events in the Archive. If the time since the last recorded
event is greater than or equal to CompMax, then PI
automatically stores the next value in the Archive,
regardless of the CompDev setting.
You typically set CompMax to the same value for all points
in the system. It's common practice to choose a CompMax
setting of one work shift (for example, 8 hours).