TYPE “KWS” COILS
Type “KWS” Coils are specifically designed and
engineered to meet most applications requiring normal
water quantities and normal water pressure drop.
Type “KWS” Coils are counterflow, single serpentine
circuited to deliver absolute maximum performance.
With single serpentine coils every tube in the first row is
fed as indicated in the circuiting drawing on the right.
Type “KWS” Coils of two, four, six, eight and ten rows
deep are furnished with the supply and return connections
on the same and of the coil.
TYPE “KWD” COILS
Type “KWD” Coils are designed for use in applications
that require high water quantities and low water pressure
drop.
“KWD” Coils are counterflow, double serpentine circuited
to maintain normal water velocities and low water
pressure drops. With double serpentine coils every tube in
the first and second rows are fed as shown in the
circuiting drawing on the eright.
Fourn and eight row coils have the supply and return
connections on the same end of the coil.
TYPE “KWH” COILS
Type “KWH” Coils are designed to produce high
capacity with limited water quantity. High capacity is
obtained from the counterflow half serpentine water
circuiting which gives higher water velocities.
With half serpentine coils every other tube in the first
row is fed as shown in the circuiting drawing on the
right.
All Type “KWH” Coils, regardless of row depth, have
both the supply and return connections on the same end
of the coil. When ordering KWH Coils, state vertical or
horizontal air flow as required.